Table C-1. Summary of Tank Database entry fields
Entry field
Description
Source
Enraf
(1)
(811, 813, 854, 873, 894, 970, 971)
1.
Enraf option is supported for 2460 firmware version 1.B0 and higher.
Field Port
The field bus port that the selected device is connected to. Up to
six field ports may be used.
Level Device Address
Enraf level device address. Each field device has its own unique
address in the range 00-99.
Temp Device Address
Use the same address as the Enraf level device.
Number of Temp Elements
“0” in case only average temperature is required. Otherwise the
total number of connected temperature elements.
In case you don’t need to monitor values for individual
temperature elements you should set this parameter to “0” in
order to avoid unnecessary load on the field bus.
Auxiliary Inputs
Free Water Level
Liquid Pressure
Middle Pressure
Vapor Pressure
Observed Density (UIn1)
Advanced
Vapor temperature
Fast polling
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......