Reference Manual
00809-0100-2460, Rev DE
October 2018
Tank Database entry fields for the Rosemount 2460 System Hub
Table 4-3. Entry fields for the Tank Database
Entry field
Description
Source
2410 Tank Hub
Rex
Rex + DAU
Pro
Pro + DAU
TRL2 RTG
TRL2 RTG + DAU
Enraf
(1)(2)
(811, 813, 854, 873, 894, 970, 971)
Whessoe
(3)(4)
(550, 660)
L&J
(5)(6)
(MCG 2000, MCG 1500XL)
Varec
(7)
(1800, 1900)
1.
Enraf option is supported for Rosemount 2460 firmware version 1.B0 and higher
Appendix C: Enraf® Device Configuration
for information on how to configure the Rosemount 2460 tank database
for Enraf devices
3.
Whessoe option is supported for Rosemount 2460 firmware version 1.D0 and higher
Appendix E: Whessoe Device Configuration
for information on how to configure the Rosemount 2460 tank
database for Whessoe devices
5.
L&J and Varec options are supported for Rosemount 2460 firmware version 1.E0 and higher
Appendix H: L&J Device Configuration
for information on how to configure the Rosemount 2460 tank database for
L&J devices
Appendix I: Varec® Device Configuration
for information on how to configure the Rosemount 2460 tank database
for Varec devices
Field port
The field bus port that the selected device is connected to. Up to six
field ports may be used.
See
“Connecting to a Rosemount 2460 System Hub” on page 30
for more information.
2410 Device Address
Modbus address for the connected Rosemount 2410 Tank Hub.
Address range 101 to 199 is recommended.
2410 Tank Position
Each tank is associated with a certain position in the tank database
of the Rosemount 2410 Tank Hub. Devices on a tank must be
configured with a tank position that refers to the actual tank where
the device is installed.
Level Device Address
Communication address for the connected level device.
For level gauges address range 1 to 99 is recommended.
Temperature Device
Address
Communication address for the connected Temperature/ATD
device.
For Temperature/ATD devices address range 101 to 199 is
recommended.
Number of Temperature
Elements
Number of temperature elements connected to the temperature
transmitter (for example a Rosemount 2240S Multi-Input
Temperature Transmitter).
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......