4.3.3
Preconditions for redundancy setup
The following conditions must be met to allow setting up two Rosemount 2460 System Hubs for
redundancy operation:
The same firmware version on both System Hubs
Firmware version 1.C0 or higher
Rosemount TankMaster version 6.D0 or higher
No warnings or errors
License;
- the same maximum number of tanks
- redundancy option enabled on both system hubs
-
the same number of Modbus TCP clients
The same modem board setup
(1)
(number of boards, modem type, and modem locations)
Hardware write protection disabled
Software write protection disabled
Basically all model codes except Housing, Cable/Conduit Connections, and Options need to be identical for
the Primary and Backup system hubs.
1.
Modem boards supported for redundancy : TRL2 Modbus, RS485, Enraf BPM
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......