80
Reference Manual
00809-0100-2460, Rev DE
October 2018
4.3.8
Redundancy setup via Web GUI
This section describes the redundancy setup for a Rosemount 2460 System Hub by using the Web
interface. The setup includes two basic steps:
Paring; two system hubs are setup as a redundant pair
Redundancy configuration; addresses and fail-over criteria are configured
Pairing
1. Log in to the Web interface as described in
“Using the web interface” on page 114
.
2. Select the Redundancy tab.
3. Expand the Pair option.
4. Verify that the other system hub is pairable, i.e. all requirements for pairing are marked with a green
button. For the system hubs to be able to pair, ensure that the preconditions are fulfilled. See
“Preconditions for redundancy setup” on page 53
for more information.
If the two system hubs (Primary and Backup) are ready for pairing, click the
Pair
button to start the syn-
chronization process.
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......