101
Reference Manual
00809-0100-2460, Rev DE
October 2018
5.4.3
Manual switch over
The Rosemount 2460 System Hubs can be manually switched over from
Active
to
Passive
device.
Using TankMaster WinSetup
The
Manual Switch Over
button may be used to test that both the Primary and Backup Rosemount
2460 System Hubs function properly as Active or Passive device. It may also be used to reset the devices
in case a Fail-over has occurred.
1. In the WinSetup workspace, right click the Rosemount 2460 icon.
2. Choose the
Properties
option and select the Redundancy tab.
3. Click the
Manual Switch Over
button.
4. Verify that the
Active
device switched to
Passive
and vice versa.
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......