3.5.6
Connecting to a Rosemount 2460 System Hub
There are several ways to connect a host system to a Rosemount 2460 System Hub:
to a Host Port using TRL2 bus
to a Host Port using RS232 or RS485
via Ethernet Eth1 port
The TRL2 Bus requires a twisted and shielded pair cable with a cross-sectional area of 0.50 to 2.5 mm
2
(AWG 20 to 14). A Rosemount 2180 Field Bus Modem (FBM) is used to connect the system hub to
TankMaster or other host computer.
A service PC can be connected to the Ethernet Eth3 port for configuration and maintenance.
For RS232 communication, wiring cross-sectional area must be at least 0.25 mm
2
(AWG 24 or similar).
The maximum length of the RS232 connection is 30 m at baud rate 4800.
for information on terminal block connections.
Table 3-4. Data rate and maximum distances for RS232 communication
Baud rate (bps)
Distance (m)
2400
60
4800
30
9600
15
19200
7.6
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......