80
Reference Manual
00809-0100-4140, Rev AA
January 2017
To perform a device restart (AMS Device Manager)
1.
Right click on the device and select
Service Tools
.
2.
Select
Maintenance
, and then click on the
Reset/Restore
tab.
3.
Click on
Restart Device
, and follow on-screen instructions to perform the restart.
To perform a device restart (LOI)
This function is not available on the Local Operator Interface.
5.5.2
Load user defaults
The function
resets variables to their ex-factory settings
(see
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
To load user defaults (using Field Communicator)
1.
From the Home screen, select
3: Service Tools
.
2.
Select
4: Maintenance
, and then (
6, 7, or 8:) Reset/Restore
.
3.
Select
2: Load User Defaults
.
4.
Follow on-screen instructions to load user defaults.
To load user defaults (AMS Device Manager)
1.
Right click on the device and select
Service Tools
.
2.
Select
Maintenance
, and then click on the
Reset/Restore
tab.
3.
Click on
Load User Defaults
.
4.
Follow on-screen instructions to load user defaults.
To load user defaults (LOI)
This function is not available on the Local Operator Interface.
5.5.3
Sensor frequency
The vibrating fork frequency is indicated in the
Sensor Frequency
device variable after
sensor compensation has been applied.
Fast Keys
3, 4, 1, 1, 1
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......