41
Reference Manual
00809-0100-4140, Rev AA
January 2017
Figure 2-5. Typical Multi-drop Network
A. HART modem
B. Power supply
The Rosemount 2140 and Rosemount 2140:SIS are set to address zero (0) at the factory,
which allows operation in the standard point-to-point manner with a 4–20 mA output
signal.
To activate multi-drop communication, the level detector address must be changed to a
number from 1 to 15 for HART Revision 5, or 1 to 63 for HART Revision 7. This change
deactivates the 4–20 mA analog output, sending it to 4 mA. It also disables the failure
mode alarm signal, which is controlled by the upscale/downscale switch position.
Failure signals in multi-dropped devices are communicated through HART messages.
2.13.1
Communicating with a multi-dropped level detector
To communicate with a multi-drop level detector, the Field Communicator or AMS Device
Manager has to be set up for polling.
Communicating with a multi-dropped device
(Field Communicator)
1.
Select
Utility
and
Configure HART Application
.
2.
Select
Polling Addresses
, and then enter
0 to 63.
Communicating with a multi-dropped device
(AMS Device Manager)
Click on the
HART modem
icon and select
Scan All Devices
.
A.
B.
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......