
42
Reference Manual
00809-0100-4140, Rev AA
January 2017
2.13.2
Changing a level detector polling address
To activate multi-drop communication, the Rosemount 2140 or Rosemount 2140:SIS poll
address must be assigned a unique number from 1 to 15 for HART 5, or 1 to 63 for HART 7.
Each device in a multi-dropped loop must have a unique poll address.
Changing the polling address (Field Communicator)
1.
From the Home screen, select
2: Configure
.
2.
Select
2: Manual Setup
>
6: HART
>
2: Communication Settings
.
3.
Change the polling address.
a.
In HART 5 mode, enter a polling address in the
1: Polling Address
screen.
b. In HART 7 mode, enter a polling address in the
2: Change Polling Address
screen.
Changing the polling address (AMS Device Manager)
1.
Right click on the device and select
Configure
.
2.
In HART 5 mode:
a.
Click on
Manual Setup
, select the
HART
tab.
b. In the Communication Settings box, enter a new polling address and click
Send
.
3.
In HART 7 mode:
a.
Click on
Manual Setup
, and then select the
HART
tab.
b. Click the
Change Polling Address
button.
4.
Carefully read the warning and click
Yes
if it is safe to apply the changes.
2.14
Configuring level detector security
There are four security methods with the Rosemount 2140 and Rosemount 2140:SIS.
Security switch
HART Lock
Configuration buttons lock
LOI password
Fast keys
2, 2, 5 or 6, 2, 2
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......