35
Reference Manual
00809-0100-4140, Rev AA
January 2017
a.
Select
VIEW CONFIG
(
).
b. Scroll down (
) until
HI SAT
and the high saturation level setting appears.
c.
Scroll down (
) until
LO SAT
and the high saturation level setting appears.
4.
Exit the menu system by either waiting one minute for the
EXIT MENU?
prompt, or
scrolling down menus to find and select
BACK TO MENU
and
EXIT TO MENU
.
Note
When messages about the loop appear, take appropriate safe action and select “
”.
See
“Configuration basics” on page 10
for further information.
2.10.3
Configuring process alerts
Note
This function is available only a Rosemount 2140 and Rosemount 2140:SIS with the
Extended Features Package enabled.
Process alerts allow the level detector to indicate when a pre-set data point is exceeded.
Alerts can be set for the following device variables:
Output State
Sensor State
Sensor Frequency
Scaled Variable (if supported)
Terminal Voltage
Electronics Temperature
An active alert is displayed on a Field Communicator, AMS Device Manager status screen or
in the error section of an LOI display. When the value returns within range, an alert is reset.
Alerts are configured by:
Alert Mode – Select “on” to enable the alert, or “off” to disable it.
High Value Alert – Defines the upper boundary limit for a device variable value.
Low Value Alert – Defines the lower boundary limit for a device variable value.
Note
The high alert value must be higher than the low alert value. Both alert values must also be
within the sensor limits.
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......