25
Reference Manual
00809-0100-4140, Rev AA
January 2017
Note
When messages about the loop appear, take appropriate safe action and select “OK”.
See
“Configuration basics” on page 10
for further information.
To change the current output type and operating mode
(AMS Device Manager)
1.
Right click on the device and select
Configure
.
2.
Select
Manual Setup
, and then select the
Analog Output
tab.
3.
If changing the current output type:
a.
Select an option for the
Current Output Type field.
b. If the type selected is
Custom
, enter output currents for ‘off’/‘on’ output states at
the
Custom Off Current
and
Custom On Current
fields.
4.
If changing the current output operating mode:
a.
Select an option for the
Current Output Operating Mode
field.
5.
Click on
Send
.
6.
Carefully read the warning and click
Yes
if it is safe to apply the changes.
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
To change the current output type and operating mode (LOI)
1.
Press any LOI button to activate the menu.
(See
for assistance with using the LOI buttons).
2.
If changing the current output type:
a.
Scroll down (
) and then select
EXTENDED MENU
(
).
b. Scroll down (
) and then select
ANALOG OUTPUT
(
).
c.
Scroll down (
) and then select
OUTPUT TYPE
(
).
d. Follow on-screen instructions and select a current output type
(“4 and 20 mA”, “8 and 16 mA”, or “Custom”).
e.
If the type selected is “Custom”, enter output currents for ‘off’ and ‘on’ output
states at the
CUSTOM OFF
and
CUSTOM ON
menus.
3.
If changing the current output operating mode:
a.
Scroll down (
) and then select
EXTENDED MENU
(
).
b. Scroll down (
) and then select
ANALOG OUTPUT
(
).
c.
Scroll down (
) and then select
OPERATE MODE
(
).
d. Follow on-screen instructions and select a current output operating mode
(“Wet on” or “Dry on”).
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......