Reference Manual
00809-0100-4140, Rev AA
January 2017
2.5
Configuration basics
The Rosemount 2140 and 2140:SIS Level Detectors (“level detectors”) can be configured
before or after installation. Configuring the point level detector before installation ensures
all level detector components are in working order before installation.
2.5.1
Setting the security switch
Verify that the security switch is set in the unlock position (
) to proceed with
configuration. See
for the switch location.
2.5.2
Setting the loop to manual
When sending or requesting data that would disrupt the loop or change the point level
detector output, set the process application loop to manual control. The Field
Communicator, AMS Device Manager, or the LOI prompts you to set the loop to manual
when necessary. The prompt is only a reminder. Acknowledging this prompt does not set
the loop to manual. It is necessary to set the loop to manual control as a separate operation.
2.6
Configure device using Guided Setup
The options available in the Guided Setup wizard include all items required for basic
operation. All basic configuration parameters are described in
2.6.1
Guided setup on the AMS Device Manager
1.
Click the
Start
button, and then select
All Programs
>
AMS Device Manager
>
AMS Device Manager
.
2.
Select
View
>
Device Connection View
.
3.
In the Device Connection View, double-click the
HART
modem icon.
4.
Double-click the device icon.
5.
From the Home screen, select
Configure
>
Guided Setup
.
6.
Select
Basic Setup
and follow the on-screen instructions.
2.6.2
Guided setup on the Field Communicator
1.
Turn on the Field Communicator.
2.
From the Main Menu, tap the HART symbol. The Field Communicator now
connects to the device.
3.
From the Home screen, select
Configure
>
Guided Setup
.
4.
Select
Basic Setup
and follow the on-screen instructions.
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......