Piping
87
Table 51
Interconnecting piping refrigerant charge
Line Size,
O.D., in.
R-22, lb/100 ft. (kg/30m)
R-407C, lb/100 ft. (kg/30m)
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
1/2
7.3 (3.3)
—
6.9 (3.1)
—
5/8
11.7 (5.3)
2.1 (1.0)
11.0 (5.0
2.2 (1.0)
3/4
16.6 (7.5)
3.0 (1.4)
15.7 (7.1)
3.1 (1.3)
7/8
24.4 (11.1)
4.4 (2.0) 23.0
(10.4) 4.5
(1.9)
1-1/8
41.4 (18.9)
7.8 (3.5) 39.3
(17.8) 7.8
(3.5)
1-3/8
63.3 (28.7)
11.8 (5.4) 59.8
(27.1 11.8
(5.4)
Table 52
R-22 and R-407C refrigerant required, approximate
Standard
Condenser
Models
Approximate R-22 Refrigerant Needed Approximate R-407C Refrigerant Needed
Dual Circuit
lb/circuit (kg/circuit)
Dual Circuit
lb/circuit (kg/circuit)
FSC or
VFD
Lee-Temp
(includes
receiver)
FSC or
VFD
Lee-Temp
(includes
receiver)
165
5 (2.3)
27 (12.3)
5 (2.3)
26 (11.8)
205
7 (3.2)
56 (25.3)
7 (3.2)
54 (24.4)
251
10 (4.6)
38 (17.2)
10 (4.6)
36 (16.3)
308
11 (5.0)
58 (26.3)
11 (5.0)
55 (24.9)
415
25 (11.3)
107 (48.4)
24 (10.9)
102 (46.2)
510
30 (13.6)
149 (67.6)
29 (13.2)
142 (64.4)
Quiet-Line Condenser Models
143
N/A
64 (29.0)
N/A
61 (27.7)
214
N/A
81 (36.7)
N/A
77 (34.9)
286
N/A
125 (56.7)
N/A
119 (54.0)
409
N/A
129 (58.5)
N/A
125 (55.8)
572
N/A
196 (88.9)
N/A
186 (84.4)