Piping Schematics
112
Figure 85 Primary connection locations—downflow, air-cooled, 105kW (30 ton), all compressor models
Point
Description
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
R
Refrigerant Access
109 (2769)
15-3/4 (400)
16-7/16" x 4 (418 x 102)
L1
Liquid Line System 1
121-3/4 (3092)
16-3/4 (425)
5/8" Cu Sweat
L2
Liquid Line System 2
118-1/8 (3000)
16-3/4 (425)
5/8" Cu Sweat
G1
Hot Gas Discharge 1
118-1/4 (3004)
14-1/4 (362)
1-1/8" Cu Sweat
G2
Hot Gas Discharge 2
115-5/8 (2937)
14-1/4 (362)
1-1/8" Cu Sweat
CD
Condensate Drain
(infrared humidifier or no humidifier)*
83-13/16 (2129)
30 (762)
3/4" FPT
Condensate Drain
(steam generating humidifier)*
83-13/16 (2129)
30 (762)
1-1/4" FPT
W/ Optional Pump
83-13/16 (2129)
30 (762)
1/2" Cu Sweat
HUM
Humidifier Supply Line
102-3/4 (2610)
31-3/4 (806)
1/4" Cu Sweat
ECS**
Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8" Cu Sweat
ECR**
Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8" Cu Sweat
E1
Electrical Conn. (High Volt)
98-1/8 (2492)
31-1/4 (794)
2-1/2"
E2
Electrical Conn. (High Volt)
91 (2311)
31-1/4 (794)
2-1/2"
LV1
Electrical Conn. (Low Volt)
2 (51)
28-1/4 (718)
7/8"
LV2
Electrical Conn. (Low Volt)
2 (51)
30-1/4 (768)
7/8"
LV3
Electrical Conn. (Low Volt)
2 (51)
32 (813)
7/8"
B1
Blower Outlet
27-7/8 (708)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
B2
Blower Outlet
52-1/16 (1322)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
B3
Blower Outlet
76-1/4 (1937)
18 (457)
14-1/2 x 15-11/16 (368 x 398)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on Dual Cooling Systems only (4 pipe system)
ECS
ECR
E1
E2
CD
B1
O
X
Y
A
A
B2
B3
HUM
R
L1 L2
G1 G2
FRONT VIEW
LV1
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
4" (102mm)
BLOWER
OUTLET
ALL DIMENSIONS FROM
REAR CORNER OF UNIT
INCLUDING PANELS
35"
(889mm)
LV2
LV3
SECTION A-A
FRONT OF UNIT
16-7/16"
(418mm)
131" (3327mm)
BLOWER
OUTLET
BLOWER
OUTLET
15-11/16"
(398mm)
DPN001014
Rev. 3