Disassembling the Liebert DS for Transport
61
Figure 49 Component dimensions—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressor
models; forward-curved and EC fan
Table 35
Component weights—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors;
forward-curved and EC fan
Component
Dry Weight, lb (kg) Approximate (Includes Panels)
Forward Curved Fans
EC Fans
Air-Cooled
Dual Cool
Air-Cooled
Dual Cool
Compressor Assembly
950 (432)
950 (432)
950 (432)
950 (432)
Filter & Electric Box Assembly
270 (123)
270 (123)
270 (123)
270 (123)
Blower & Coil Assembly
1820 (827)
2180 (991)
1560 (708)
1915 (870)
37"
(940mm)
59-7/16"
(1510mm)
DPN001057
Rev. 1
131" (3327mm)
Assembled Length
33"
(838mm)
26"
(660mm)
105" (2667mm)
76"
(1930mm)
76"
(1930mm)
Assembled
Height
39"
(991mm)
41-11/16"
(1059mm)
Filter and Electric Box Assembly
Compressor Assembly
Blower and Coil Assembly
Drawing views are simplified
with panels removed to show
overall dimensions.
See disassembly and handling
instructions in installation manual.
Содержание Liebert DS Series
Страница 1: ......
Страница 2: ......
Страница 164: ...HVAC Maintenance Checklist 154 NOTES ...
Страница 165: ...HVAC Maintenance Checklist 155 ...
Страница 166: ...HVAC Maintenance Checklist 156 ...