Liebert DS Dimensions and Weights
27
Figure 22 Floor stand dimensions—downflow, 28-42kW (8-12 ton) models
Table 19
Floor stand and floor planning dimensions—downflow, 28-42kW (8-12 ton) models
Dimensions, in. (mm)
Height, in. (mm)
Model
A
B
C *
D Turning Vane
Air-Cooled Semi-Hermetic Models and
All Water/Glycol/GLYCOOL Models
85
(2159)
26
(660)
9 (229)
4 (111)
12 (305)
7 (187)
15 (381)
10 (264)
Air-Cooled Scroll Models and
Air-Cooled Digital Scroll Models
72
(1829)
13
(330)
18 (457)
13 (340)
21 (533)
16 (416)
24 (610)
19 (492)
DPN000820
REV 2
Right side of paneled unit is flush
with right side of floor stand. All other
paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm)
adjustment from nominal height C.
Gussets supplied on floor stands
12" (305 mm) tall and greater
Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.
Supply air
discharge
opening
Optional turning vane