Piping Schematics
110
Figure 83 Primary connection locations—downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all
compressor models
Point
Description
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
W
Water/Glycol/GLYCOOL Access
103 (2616)
9 (229)
3-1/2 x 8 (89 x 203)
WS
Water/Glycol/GLYCOOL Supply
104-3/4 (2661)
11 (279)
2-1/8" Cu Sweat
WR
Water/Glycol/GLYCOOL Return
104-3/4 (2661)
15 (381)
2-1/8" Cu Sweat
CD
Condensate Drain
(infrared humidifier or no humidifier)*
69-1/4 (1759)
30 (762)
3/4" FPT
Condensate Drain
(steam generating humidifier)*
69-1/4 (1759)
30 (762)
1-1/4" FPT
W/ Optional Pump
69-1/4 (1759)
30 (762)
1/2" Cu Sweat
HUM
Humidifier Supply Line
76-1/2 (1943)
29 (736)
1/4" Cu Sweat
ECS**
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8" Cu Sweat
ECR**
Econ-O-Coil Return
72 (1829)
29 (737)
2-1/8" Cu Sweat
E1
Electrical Conn. (High Volt)
78-1/2 (1994)
31-1/8 (790)
2-1/2"
E2
Electrical Conn. (High Volt)
75-3/8 (1915)
31-1/8 (790)
2-1/2"
LV1
Electrical Conn. (Low Volt)
1-7/8 (48)
28-1/2 (724)
7/8"
LV2
Electrical Conn. (Low Volt)
1-7/8 (48)
30-1/4 (768)
7/8"
LV3
Electrical Conn. (Low Volt)
1-7/8 (48)
32 (813)
7/8"
B1
Blower Outlet (15 x 15)
23-1/8 (587)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
27-3/4 (705)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
B2
Blower Outlet (15 x 15)
50-3/8 (1280)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
54-3/8 (1381)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
*
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials.
The drain line must comply with all local codes.
** Supplied on Dual Cooling Systems only (4 pipe system)
W
WS
WR
O
X
Y
A
A
8"
(203mm)
NOTE: Drawing not to scale.
Tolerance on all piping
dimensions is ± 1/2" (13mm).
FRONT OF UNIT
DPN00933
Rev. 4
FRONT VIEW
SECTION A-A
All dimensions from
rear corner of unit
including panels
ECS
ECR
E1 E2
HUM
CD
B1
LV1
LV2
LV3
BLOWER
OUTLET
BLOWER
OUTLET
B2
109" (2769mm)
3-1/2"
(89mm)
35"
(889mm)
16-1/16"
(408mm)