Piping Schematics
114
Figure 87 Primary connection locations—downflow, water/glycol/GLYCOOL, 105kW (30 ton), all
compressor models
Point
Description
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
W
Water/Glycol/GLYCOOL Access
125-15/16 (3199)
9 (229)
3-1/2 x 8 (89 x 203)
WS
Water/Glycol/GLYCOOL Supply
127-7/8 (3248)
10-1/16 (256)
2-1/8" Cu Sweat
WR
Water/Glycol/GLYCOOL Return
127-7/8 (3248)
13-1/4 (337)
2-1/8" Cu Sweat
CD
Condensate Drain
(infrared humidifier or no humidifier)*
83-13/16 (2129)
30 (762)
3/4" FPT
Condensate Drain
(steam generating humidifier)*
83-13/16 (2129)
30 (762)
1-1/4" FPT
W/ Optional Pump
83-13/16 (2129)
30 (762)
1/2" Cu Sweat
HUM
Humidifier Supply Line
102-3/4 (2610)
31-3/4 (806)
1/4" Cu Sweat
ECS**
Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8" Cu Sweat
ECR**
Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8" Cu Sweat
E1
Electrical Conn. (High Volt)
98-1/4 (2496)
30 (762)
2-1/2"
E2
Electrical Conn. (High Volt)
88-7/16 (2246)
30 (762)
2-1/2"
LV1
Electrical Conn. (Low Volt)
2 (51)
27-1/2 (796)
7/8"
LV2
Electrical Conn. (Low Volt)
2 (51)
30-1/4 (768)
7/8"
LV3
Electrical Conn. (Low Volt)
2 (51)
32 (813)
7/8"
B1
Blower Outlet
28-1/4 (718)
18 (457)
14-1/2 x 15-7/8 (368 x 403)
B2
Blower Outlet
52 (1321)
18 (457)
14-1/2 x 15-7/8 (368 x 403)
B3
Blower Outlet
75-11/16 (1922)
18 (457)
14-1/2 x 15-7/8 (368 x 403)
*
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual Cooling systems only (4 piping system).
A
A
ECS
ECR
E1
E2
CD
B1
O
X
Y
B2
B3
HUM
W
WS
WR
FRONT VIEW
LV1
NOTE: Drawing not to scale.
Tolerance on all piping
dimensions is ± 1/2" (13mm).
3-1/2"
(89mm)
BLOWER
OUTLET
ALL DIMENSIONS FROM
REAR CORNER OF UNIT
INCLUDING PANELS
35"
(889mm)
LV2
LV3
SECTION A-A
FRONT OF UNIT
15-7/8"
(403mm)
TYP
131" (3327mm)
BLOWER
OUTLET
BLOWER
OUTLET
14-1/2"
(368mm)
TYP
8"
(203mm)
DPN001015
Rev. 3
Содержание Liebert DS Series
Страница 1: ......
Страница 2: ......
Страница 164: ...HVAC Maintenance Checklist 154 NOTES ...
Страница 165: ...HVAC Maintenance Checklist 155 ...
Страница 166: ...HVAC Maintenance Checklist 156 ...