Liebert DS Dimensions and Weights
11
Figure 6
Cabinet and floor planning dimensions—downflow, air-cooled, 28-42kW (8-12 ton),
semi-hermetic compressor models
Table 3
Weights for downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
Model No.
Dry Weight - lb. (kg),
Approximate
028, 035, 042
Air-Cooled
1780 (809)
Dual-Cool
1930 (877)
DPN000795
Rev. 3
Secondary Refrigerant
Piping Entrance
Opening
56-7/8"
(1445mm)
Air Inlet Opening
Top View
86"
(2184mm)
Secondary Entrance
High Volt Connection(s)
35"
(889mm)
33"
(838mm)
76"
(1930mm)
2"
(51mm)
Front View
85"
(2159mm)
Shaded areas indicate a
recommended minimum
clearance for component
access.
34"
(864mm)
15"
(381mm)
Bezels
Minimum clearance
required for filter
replacement
3/4"
(19mm)
Secondary Entrance
Low Volt Connections
Opening
24-3/8"
(619mm)
Filters are accessible
through top of unit onl y.
Downflow electrical
connections can be made
from top or bottom of unit.
Notes: