Maintenance
149
13.14.3Drycooler Settings
Applications with the Optional Stat Setting require field piping to be insulated to prevent
condensation.
Table 66
shows acceptable applications where stats must be adjusted to Optional
Setting. Aquastats must be field-adjusted to Optional Setting for:
• GLYCOOL/Dual Cool applications
• Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all
Liebert DS units with digital compressors). These units have a “D” or “G” in the seventh
character: DS/VS/xxxx
D
or DS/VS/xxxx
G
.
Table 66
Water/glycol system conditions requiring optional settings for aquastats
Cooling Type
Glycool
Glycol
Flow Control
MBV
WRV
MBV
WRV
Drycoolers in Loop
1
Multiple
1
Multiple
1
Multiple
1
Multiple
Stat Setting*
Optional
Optional
Optional
Optional
Optional
Factory
Factory
Factory
Insulate Field Piping
Yes
Yes
Yes
Yes
Yes
No
No
No
* See
Tables 67
through
69
MBV=motor ball valve; WRV=water regulating valve
Table 67
Aquastat settings—two-fan through four-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
Aquastat #
Fans
Factory Setting
(Glycol) (see Notes 1 and 2)
Optional Setting
(GLYCOOL) (see Note 3)
AQ1
F1
65°F (18.3°C)
35°F (1.7°C)
AQ2
F2 & F3
75°F (23.9°C)
45°F (7.2°C)
AQ3
F4
70°F (21.1°C)
40°F (4.4°C)
Table 68
Aquastat settings—six-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
Aquastat #
Fans
Stat Location
Cabinet
Factory Setting
(Glycol) (see Notes 1 and 2)
Optional Setting
(GLYCOOL) (see Note 3)
AQ1
F1
Main
65°F (18.3°C)
35°F (1.7°C)
AQ2
F2
Main
70°F (21.1°C)
40°F (4.4°C)
AQ3
F3 & F4
Auxiliary
73°F (22.8°C)
43°F (6.1°C)
AQ4
F5 & F6
Auxiliary
75°F (23.9°C)
45°F (7.2°C)
Table 69
Aquastat settings—eight-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
Aquastat #
Fans
Stat Location
Cabinet
Factory Setting
(Glycol) (see Notes 1 and 2)
Optional Setting
(GLYCOOL) (see Note 3)
AQ1
F1
Main
65°F (18.3°C)
35°F (1.7°C)
AQ2
F2
Main
70°F (21.1°C)
40°F (4.4°C)
AQ3
F3 & F4
Auxiliary
73°F (22.8°C)
43°F (6.1°C)
AQ4
F5 & F6
Auxiliary
75°F (23.9°C)
45°F (7.2°C)
AQ5
F7 & F8
Main
78°F (25.6°C)
48°F (8.9°C)
NOTE
1. All drycoolers are shipped at Factory Setting.
2. Factory Setting is used for all glycol applications, except single drycooler loops with motor
ball valve controls.
3. Stats must be field-adjusted to Optional Setting for GLYCOOL/Dual Cool applications
and all single drycooler loops using motor ball valve flow controls.