Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
February 2019
Parameter Menu
Table 12.
Binary Inputs Parameter Group (1)
Menu Item
Sub Menu Item
Poss. Setting
Notes / Comments
P9.1
Binary Input
Input 1
0: no function
This input has no function
1: Open
OPEN command in REMOTE mode (selector switch in position
REMOTE).
2: Closed
CLOSED command in REMOTE mode (selector switch in
position REMOTE).
3: Stop
STOP command in REMOTE mode (selector switch in position
REMOTE).
4: Open Self-hold
Self-hold for OPEN, i.e., a short pulse is sufficient and the
actuator moves then into the end position. Use the STOP
command to stop the actuator.
5: Closed Self hold
Self-hold for CLOSED, see OPEN SELF-HOLD
6: Emergency
Open
Superimposed run command; run the actuator in direction
OPEN regardless of whether the selection switch is set to
REMOTE or LOCAL operation
7: Emergency
Closed
Superimposed run command; run the actuator in direction
CLOSED regardless of whether the selection switch is set to
REMOTE or LOCAL
8: Release
The actuator may be operated only with a switched signal.
Both in local and remote operation
9: Open/Closed
The actuator moves towards OPEN if input is active and
towards CLOSED otherwise
10: Close/Open
The actuator moves towards CLOSED if input is active and
towards OPEN otherwise
11: Positioner
Release of the postioner
12: Open inv.
As open but active low
13: Close inv.
As CLOSED but active low
14: Stop inv.
As STOP but active low
15: Open
Self-Hold.inv
As Open Self-Hold but active low
16: Closed
Self-Hold inv
As Closed Self-Hold. but active low
17: Emergency-
Open inv.
As Emergency-Open but active low
18: Emergency-
Closed inv.
As Emergency-Closed but active low
19: Block
With activated (switched) signal, the actuator is locked for
operation also in local mode
20: Contoller lock
Positioner lock
21: Release Local
The actuator may be operated only with a switched signal.
22: Block Local
As Release Local but active low
23: Lock Open
Trigger lock OPEN (in LOCAL and REMOTE mode). Actuator
moves with the highest priority to OPEN; command
continues internally active after reaching the end position
OPEN. Dropping only with LOCK OFF, Supply OFF or operating
mode OFF.
24: Lock Closed
Trigger lock CLOSED (in LOCAL and REMOTE
mode). Actuator moves with the highest priority to
CLOSED; command continues internally active
after reaching the end position CLOSED. Dropping
only with LOCK OFF, Supply OFF or operating
mode OFF.
25: Lock Off
Drop the lock
26: Failsafe
Trigger the failsafe function in all operating modes
(only functional in Failsafe actuators).
27: Failsafe inv.
As Failsafe, but active low
28: Lock Open inv.
As Lock Open, but active low
29: Lock Closed inv.
As Lock Closed, but active low
30: Lock Off inv.
As Lock Off, but active low