45
Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
February 2019
Parameter Menu
8.9
Parameter Group: Binary Outputs
The controller is equipped with 8 freely configurable binary outputs. Please find further
information on technical data of the binary outputs in Section 17.1. Provided with external
supply, binary outputs are optically isolated from the rest of the controller.
Default binary outputs are as follows:
•
Output 1: Ready
•
Output 2: End position OPEN
•
Output 3: End position CLOSED
•
Output 4: Run OPEN
•
Output 5: Run CLOSED
•
Output 6: Torque
•
Output 7: LOCAL
•
Output 8: REMOTE
Table 14.
Binary Outputs Parameter Group (1)
Menu
Item
Sub Menu
Item
Poss. Setting
Notes / Comments
P10.1
Binary
Output
Output 1
0: User defined
Optional
1: Ready
Actuator is ready
2: Fault
General fault; actuator is not ready
3: Open
Actuator is in open position
4: Closed
Actuator is in closed position
5: Running Open Actuators runs in direction Open
6: Running
Closed
Actuators runs in direction Closed
7: Runing
Actuator is running in either Open or Closed
8: Torque Open
Switch off torque was reached in Open direction-
actuator has been switched off
9: Torque Closed
Switch off torque was reached in Closed direction-
actuator has been switched off
10: Torque
Switch off torque was reached in either Closed or
Open direction
11: Travel Open
The Open end postion has been reached
12: Travel Closed The Closed end postiion has been reached
13: Pos. > Int.1
Position > Intermediate position 1
14: Pos. < Int.1
Position < Intermediate position 1
15: Pos. > Int.2
Position > Intermediate position 2
16: Pos. < Int.2
Position < Intermediate position 2
17: Pos. > Int.3
Position > Intermediate position 3
18: Pos. < Int.3
Position < Intermediate position 3
19: Pos. > Int.4
Position > Intermediate position 4
20: Pos. < Int.4
Position < Intermediate position 4
21: Local
Local operating mode (selector switch in position)