49
Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
February 2019
Parameter Menu
Table 18.
Position Output Parameter Group
Menu item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P11.1
Position Output Function 1
0: off
mA output disabled
1: Position mA output corresponds to the actual position value.
2: Pos.
Valvencahr.
mA output corresponds to the actual position value
taking into account the valve characteristic.
3: Torque 1
mA output corresponds to the actual torque value.
torque = 100% Close: mAoutput = start
torque = 0%: mAoutput = center
torque = 100% Open: mAoutput = end
4: Torque 2
mAoutput corresponds to the actual torque value.
torque = 100% Close: mAoutput = end
torque = 0%: mAoutput = start
torque = 100% Open: mAoutput = end
5: Torque 3
mAoutput corresponds to the actual torque value.
torque = 150% Close: mAoutput = start
torque = 0%: mAoutput = center
torque = 150% Open: mAoutput = end
6: Torque 4
mAoutput corresponds to the actual torque value.
torque = 150% Close: mAoutput = end
torque = 0%: mAoutput = start
torque = 150% Open: mAoutput = end
P11.2
Position Output Start 1 (at 0%)
0 - 20,5
mA
{4mA}
mA value for the Closed (0%) position
P11.3
Position Output End 1 (at 100%)
0 - 20,5
mA
{20mA}
mA-value for the On (100%) position
P11.4
Position Output Calib. 20mA
-10% -
+10% see
Output 1
Calibrating the output position during the setting of
this parameter will output a 20mA (100%) signal. Use
this parameter to calibrate accurately the 20mA output
signal. (e.g., if you measure 19.8 mA at the output, just
add 1% (0.2 mA. . . 1% of 20mA) to the displayed value)
P11.5
Analog Output
Function 2
see
Function 1
P11.6
Analog Output
Begin 2 (at
0%)
see Begin
1
P11.7
Analog Output
End 2 (at
100%)
see End 1
P11.8
Analog Output
Calib. 20 mA 2
see Calib.
20 mA 1