Section 6: Commissioning
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Febraury 2019
Commissioning
Section 6: Commissioning
It is assumed that the actuator has been installed and electrically connected correctly.
(See Section 5).
NOTE:
Remove silica gel from the alarm cover.
6.1
General Information
NOTE:
When commissioning and each time after dismounting the actuator, the positions have to
be reset (see Section 6.4).
6.2
Manual Operation
There is no way to operate this actuator design manually.
6.3
Mechanical Default Settings, Preparation
The use of multi-turn sensors makes mechanical settings unnecessary.
CAUTION: OBSERVE CORRECT PROCEDURE
Before the motorised operation of the valve, it is essential to check and adjust
torque settings.