Set Pr
00.004
at the required rate of deceleration. Note that larger values produce lower
deceleration. The rate applies in both directions of rotation.
* With Unidrive M201, the default is Pad (5).
Use Pr
00.005
to select the required frequency/speed reference as follows:
00.004 {02.021}
Deceleration Rate 1
RW
Num
US
OL
Ú
±
VM_ACCEL_RATE s/100 Hz
Ö
10.0 s/100 Hz
RFC-A
00.005 {11.034}
Drive Configuration
RW
Txt
PT
US
OL
Ú
AV (0), AI (1), AV.Pr (2), AI.Pr (3),
Preset (4), Pad (5), Pad.Ref (6),
E.Pot (7), torque (8), Pid (9)
Ö
AV (0)*
Value
Text
Description
0
AV
Analog input 1 (voltage) Analog input 2 (voltage) selected by terminal
(Local/Remote)
1
AI
Analog input 1 (current) or Analog input 2 (voltage) selected by terminal
(Local/Remote)
2
AV.Pr
Analog input 1 (voltage) or 3 presets selected by terminal
3
AI.Pr
Analog input 1 (current) or 3 presets selected by terminal
4
Preset
Four presets selected by terminal
5
Pad
Keypad reference
6
Pad.Ref Keypad reference with terminal control
7
E.Pot
Electronic Potentiometer
8
torque
Torque mode, Analog input 1 (current frequency reference) or Analog input 2
(voltage torque reference) selected by terminal
9
Pid
PID mode, Analog input 1 (current feedback source) and Analog input 2
(voltage reference source)
A change to Pr
00.005
is set by pressing the MODE key on exit from parameter edit mode.
The drive must be disabled, stopped or tripped for a change to take place. If Pr
00.005
is
changed while the drive is running, when the MODE key is pressed on exit from parameter
edit mode, Pr
00.005
will change back to its previous value.
When the setting of Pr
00.005
is changed, the appropriate drive configuration parameters
are set back to their default values.
NOTE
NOTE
Unidrive M200 201 Quick Start Guide English Iss6.book Page 33 Thursday, September 10, 2015 1:48 PM