Unidrive M200-201 Quick Start Guide
23
Issue Number: 6
Figure 4-18 Pr 00.005 = Pid (60 Hz)
4.5 EMC
4.5.1
Internal EMC filter
It is recommended that the internal EMC filter be kept in place unless there is a specific reason for
removing it. If the drive is used as a motoring drive as part of a regen system, then the internal EMC
filter must be removed.
The internal EMC filter reduces radio-frequency emission into the line power supply.
For longer motor cables, the filter continues to provide a useful reduction in emission levels and
when used with any length of shielded motor cable up to the limit for the drive, it is unlikely that
nearby industrial equipment will be disturbed. It is recommended that the filter be used in all
applications unless the instructions given above require it to be removed, or where the ground
leakage current is unacceptable.
4.5.2
Removing the internal EMC filter
The supply must be disconnected before removing the internal EMC filter.
1
2
4
0V
0-10 V PID
Reference input
4 - 20 mA PID
feedback input
PID feedback
input (AI 1)
PID reference
input (AI 2)
5
+ 10 V output
7
9
10
Digital output
(zero frequency)
Not stop
11
12
13
14
Jog forward
Run
Analog output 1
(motor frequency)
PID enable
+ 24 V output
When Pr
00.005
is set to Pid, the following parameters may
need to be adjusted:
• PID proportional gain*
• PID integral gain*
• PID feedback invert*
• PID output upper limit (%)*
• PID output lower limit (%)*
* Refer to
Drive User Guide.
WARNING
Unidrive M200 201 Quick Start Guide English Iss6.book Page 23 Thursday, September 10, 2015 1:48 PM