11
Annex
Page 140
gas-lab
Q1
H801 User lock open
The
User lock
consists of one numerical lock for each of the two contract parties. The
locks are optional and defined via the device parameterisation. They are opened and
closed via a special operator panel menu. The
User lock open
hint is generated if all
defined locks are open.
Open locks enable the user to access particular parameters or actions, either via the
operator panel of the device or with GAS-WORKS via the data interface.
H802 Revision
When the revision /service switch is set, the gas-net Q1 responds as follows: The hint
“Revision” is created. From this moment, all entries in the interval archive are marked
revision. The device is in revision mode. The revision switch is set automatically in case of
basic calibration and test gas injection. The revision switch is implemented in software and
can also be opened from the operator panel of the device.
H1931 Logbook service request / H1932 Archive service request
Hints H1931 and H1932 are generated when a logbook or an archive has exceeded a
certain size. Please refer to
Technische Spezifikation für DSfG-Realisierungen (Technical
Specification for DSfG Implementations)
for further details.
H 2002 No pressure
The hint is generated after 5 seconds, without pressure when the measurement system
gas pressure expects.
H 2003 P min
The hint is generated along with alarm A605 (data error) when the lower alarm limit is
violated.
H 2004 P max
The hint is generated along with alarm A605 (data error) when the upper alarm limit is
violated