1.4 With (H1)
blue light
on and
red light
(H3)off in the remote cooling unit and there is
still alarm blinking E11 in the main board :
1.
Check electric wiring in the main board J6 (disconected and claen and reconnect)
2.
If the electric wirings on J6 are clean and there is still the alarm blinking, change the main board.
.
.
.
.
Allarm E10
(
alarm Pressostat compressor
) :
Electric wirings closes between AP & AP in the terminal board (as electric wiring diagram)
1.
Check as 1.1 -1.2 1.3/3 from page 1
2.
Check the supply (24V) between A1 and A2 of the coil 1K4 with digital multimeter as electric wiwring diagram (picture 1)
3.
With power supply (24) in the coil 1k4 check the electric wiring 1-4 in the pressostat .(picture2)
.
.
.
.
.