Technical Bulletin
Identification:
Bulletin no:
Date:
Issuer:
Factory:
E6-E7
VT
X
2006-07
19-09-06
Customer Support Dept.
Pordenone (Italy)
ELECTROLUX PROFESSIONAL
p. 1 of 1
Subject:
Reset Led service alarm
Model:
BC-BCF Length wise “
only cruise version
”
Problem:
Led service alarm always ON without alarm storage
Reason:
In some conditions can happen that led of alarm stay
always on, due to appliance switch off the during a cycle .
Action in
Factory:
Resetting the FACT parameter
Action in
Field:
Resetting the FACT parameter
When the condition above descript appear follow this instruction:
1. Press the button
until the led
is On (light orange)
2. Keep press for 5 second together buttons
until in the display appear the
label “FACTORY”
3. Keep press together the buttons
+
until appear in the display the label
“RES” and all led of the user main are on.
4. Release the buttons and the led
will be off.
#
in any case checked all parameters with parameters list
VIALE TREVISO, 15 – 33170 PORDENONE – ITALY
TELEPHONE:
TELEFAX:
E-MAIL:
+ 39 0434 380 710
+ 39 0434 380 740
Содержание BLAST CHILLER LW
Страница 1: ...BLAST CHILLER LW 595R18700 ...
Страница 3: ...Electronic control Cruise version CRUISE version ...
Страница 53: ...Blast Chiller or Freezer First point installation Code check Safety device Description ...
Страница 92: ...Remote cooling unit information What you must know to respect a correct installation ...
Страница 102: ... T1 T2 AP AP AT AT Electrical connection Find the terminals inside the electrical box ...