ERROR CODE
E10
:
HIGH PRESSURE CIRCUIT WARNING
This type of Alarm is activated by the digital input J6 (3-4) on
the main board and it causes an interruption of the working
cycle in progress. It generates an alarm connected with the
pressure switch. The display on the user interface shows the
ERROR codes. This condition causes the following event:
¾
The red Alarm Service Led is flashing
¾
The buzzer is active
¾
The display shows the ERROR code
“
E10
”
ALARMS CONDITIONS
The alarm occurs when one of those conditions is satisfied:
¾
during the execution of any working cycle (chilling, freezing
or maintenance) the number of times that the pressure
switch is activated is over than the parameter
“
PAL
”
(Pressostat Active Times)
¾
during any working cycle (chilling, freezing or maintenance)
the pressure switch is ON more than the value
“
PAt
”
(Pressostat Active Time minutes)
¾
the condenser is dirty
CAUSES
- 72 -