Heating
Two Stage Heating
Heat pump units accommodate two-stage heating when
optional electric heater is present in combination with heat
pump condenser.
First stage consists of heat pump alone and second stage
consists of heat pump and electric heat both operating
simultaneously.
To verify heating operation, place Amp meter on indoor
incoming power line.
1.
Set mode at heating, with thermostat set 1° above
current room temperature.
• Compressor will start and deliver heat to conditioned
space, Amp meter registers fraction of Amp (blower
motor only).
2.
Set thermostat 2° above current room temperature.
Compressor continues to operate, delivering heat to
conditioned space, electric heat will energize.
• Amp meter now reads 7 to 13 Amps at 230 volts
AC dependent upon electric heater capacity and line
voltage supplied to air handler.
electric Heat Applications
Electric heat units utilize control relay located on circuit
board in control box.
• Control calls for electric heat relay energizes
Auto-reset limit switch located on heater end plate
or on heater assembly interrupts power to heater if
overheat condition occurs.
• Electric heat assembly is equipped with one-time fuse
link. When electric heat temperatures rise above auto
resetting limit switch, non-resetting, one-time fusible
link opens heater remains “OFF”.
• To restart, new fuse link is required. Do not replace
fusible link with simple wire conductor.
• Following current values apply when unit is connected
to 230v power supply.
• values include fan motor current. If supply voltage is
different, amperage changes.
3kw = 13.5 Amps
1.5kw= 6.9 Amps
Indoor unit contains electronic anti-short-cycle timer
feature (ASCT) which prevents outdoor condenser from
short cycling.
After control is satisfied there is a three (3) minute delay
before condenser is allowed to restart.
Wired wall control is calling for cooling and ASCT delay
has elapsed, 24 vac can be measured between terminals:
electric Heat (Optional)
Units with electric heat use control relay located on circuit
board in control box. Thermostat is calling for electric
heat relay energizes.
Check for electric heat operation, place wall thermostat
in Heat mode with setpoint temperature above room
temperature.
1.
Place clamp-on type ammeter on one leg of incoming
power supply.
2.
Amp reading should correspond with values found in
#3 below, when unit is working correctly.
3.
The following current values apply when the unit is
connected to a 230 vac power supply. These values
include fan motor current. If the supply voltage is
different, this will affect the amp draw of the heater.
3kw = 13.5 Amps
1.5kw= 6.9 Amps
4.
verify electric heat relay by placing voltmeter across
high-voltage relay output terminal and incoming
power L2 terminal.
5.
Reading is same as measured across incoming power
supply if unit is working correctly.
TRoUBLESHooTInG - CAHV UnITS
Auto-reset limit switch is located on heater assembly.
1.
Limit interrupts power to heater if over-temperature
condition occurs.
2.
Limit switch is equipped with one-time fuse link.
3.
Should electric heat temperatures rise above auto
resetting limit switch, non-resetting, one-time fuse link
opens and heater remains off.
4.
Limit switch assembly must be replaced if fuse link
opens.