16
Condenser Cassette
Pairing
Line Charge
Per foot
factory
Charge
S1Cv9000
CAHv09
.25 oz./ft (23 g/m) 39.5oz (1120g)
S1Cv2000
CAHv12
.25 oz./ft (23 g/m) 39.5oz (1120g)
S1Cv8000
CAHv18
.64 oz./ft 59 g/m)
54.0oz (1531g)
S1Cv4000
CAHv24
.64 oz./ft (59 g/m) 54.0oz (1531g)
S1Cv3000
CAHv30
.64 oz./ft (59 g/m) 90.0oz (2551g)
S1Cv6000
CAHv36
.64 oz./ft (59 g/m) 90.0oz (2551g)
S1Hv9000
CAHv09
.25 oz./ft (23 g/m) 39.5oz (1120g)
S1Hv2000
CAHv12
.25 oz./ft (23 g/m) 39.5oz (1120g)
S1Hv8000
CAHv18
.64 oz./ft (59 g/m) 54.0oz (1531g)
S1Hv4000
CAHv24
.64 oz./ft 59 g/m)
54.0oz (1531g)
S1Hv3000
CAHv30
.64 oz./ft (59 g/m) 90.0oz (2551g)
S1Hv6000
CAHv36
.64 oz./ft (59 g/m) 90.0oz (2551g)
RefRIgeRAnT PROCeSSIng
Use following example to find charge adjustment and
system charge for any air handles and tubing length.
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Line Adjustment
Round to nearest ounce and allow for gauges and hoses.
Table 6 - S1CV / S1HV R410A Refrigerant
Charge Table