25
1.
Remove adjacent ceiling tile to access condensate
pump cover panel.
2.
Insert squeeze water bottle nozzle through opening in
condensate pump access panel and fill drain pan. See
Figure 36.
3.
Adding water activates float switch and pump.
Water must flow regularly when condensate pump is
energized. If water does not, check pipe slope or see if
there are any pipe restrictions.
4.
verify all covers, panels and filters are in place and
discharge louvers are correctly positioned.
nOTICe
Unit is equipped with safety switch. Pump is
activated when condensate reaches critical level.
Safety switch de-energizes compressor if water level
becomes too high.
Check Cooling operation
Cooling-only systems — Turn system power on and turn
down system setpoint to activate compressor.
Check Heat pump operation
1.
Heat pump systems — Turn system setpoint up to
activate heat pump (compressor) operation.
2.
Place system controls into heating mode, with setpoint
1°F above room temperature; or meeting requirements
for 1st stage heating operation. verify compressor
start, noise, vibration, and overall system operation.
3.
Change setpoint until 2nd stage of heat is called (>2°F
(1°C) above ambient temperature).
Two stage heating requires optional electric heat.
figure 36 - Checking Condensate pump
Operation
InITIAL START-Up — CAHV UnITS
WARnIng
Electrical shock hazard. Turn off power to indoor and
outdoor units before proceeding. Failure to follow
these instructions could result in death or serious
injury.
!