A/C Condenser With Electric Heat operation
Configure wired wall controller operation with optional elec-
tric heat control - Heat Source ON.
Wired Wall controller’s call for electric heat operation - (On
or Off).
Place system switch in Heat mode after connecting
thermostat to unit.
• Adjust set-point temperature above room temperature.
• Electric heat energizes with indoor fan motor.
• Heating continues as long as set-point remains above
room temperature.
Place set-point temperature below room temperature.
Electric heater switches off and indoor fan remains on for
additional sixty (60) seconds.
optional Heat pump With Electric Heat (Two-
Stage Heating)
Control must be properly configured, Heat Source ON and
Heat Pump ON for wired wall control operation of two-stage
heating including heat pump condenser and optional indoor
electric heat. See Figure 43, pg. 33.
Wired Wall controls call for electric heat operation (On or
Off), and compressor (heat pump) heating.
Place system in Heat mode after configuring wired wall
control.
• Adjust set-point temperature above room temperature.
Compressor and fan motors start and heating begins.
• Electric heat also energizes when deviation between
room temperature and set point temperature exceeds
2°F (1°C for sixty (60) seconds) to call for second
stage heating. A 1°F (0.5°C) difference between room
conditioners & set point will only call 1st stage heat (HP
Compressor)
• Place set-point temperature below room temperature.
• Outdoor condenser and electric heat stop while indoor
fan remains on for additional sixty (60) seconds.
OPTIOnAl (CAHV) WIReD WAll COnTROlleR OPeRATIOn
nOTICe
Once cooling has cycled off or following power
outage, compressor will not start for at least three
(3) minutes (short-cycle protection).