9.0 DIAGNOSTICS & TROUBLESHOOTING
9.3 Status and Diagnostic Codes
Diagnostics
The error codes below will be displayed at the EcoNet™ Control Center under Service window / Current Faults
or in the Fault History and will be time and date stamped. VSODC (Variable Speed Outdoor Unit Control –
EcoNet™ control board) fault code is what will be displayed on the VSODC.
A952_O Outside Tempera
-
ture Thermistor Failure
•
Outdoor Temperature Thermistor
is either Open, Shorted or Low
•
Check Connection at VSODC.
•
Verify leads to sensor are not pinched, or
damaged.
•
Check sensor resistance/temp.
A953_O Coil Temperature
Thermistor Failure
(Formerly called Evap Tem
-
perature Thermistor)
•
Coil Temperature Thermistor is
either Open, Shorted or Low
•
Until will run in cooling mode, but
will not run in heating mode
•
Check Connection at VSODC.
•
Verify leads to sensor are not pinched, or
damaged.
•
Check sensor resistance/temp.
A954_O Suction Tempera
-
ture Thermistor Failure
•
Suction Thermistor is either
Open, Shorted or Low
•
Until will run in cooling mode, but
will not run in heating mode
•
Check Connection at VSODC.
•
Verify leads to sensor are not pinched, or
damaged.
•
Check sensor resistance/temp.
T955_O Compressor Tem
-
perature Thermistor Failure
•
Suction Thermistor is either
Open, Shorted or Low
•
Stator heat will not operate
•
Check Connection at VSODC.
•
Verify leads to sensor are not pinched, or
damaged.
•
Check sensor resistance/temp.
A956_O Suction Pressure
Sensor Failure
•
Suction Transducer is either,
shorted, grounded or open or
outside of acceptable range
•
Check Transducer usin formula.
•
PSIA= 375*(DCVout/DCVin)-22.8.
•
PSIG=PSIA-14.7.
•
Verify Connections at VSODC and Transucer.
T957_O Low Refrigerant
Pressure
•
Pressure at Transducer has
fallen below 50 PSIG
•
Check Refrigerant Charge
•
Check for Restrictions in liquid or suction
lines, drier, strainers etc.