4.0 INSTALLATION
Table 2A: Refrigerant Line Sizing Chart (English Units)
Unit Size
Allowable
Liquid Line
Size
mm [in.]
Allowable
Suction Line
Size
mm [in.]
Outdoor Unit ABOVE or BELOW Indoor Unit
Equivalent Length (Meters)
<8
8-15
16-23
24-30
31-38
39-46
Maximum Vertical Rise (Outdoor Unit Below Indoor Unit)* / Capacity Multiplier
7.0 KW
[2.0 Ton]
*SEE
NOTE 3
6.35 [1/4] 15.88 [5/8]
8 / 1.00
15 / 0.99 10 / 0.98
1 / 0.97
NR
NR
7.94 [5/16] 15.88 [5/8]
8 / 1.00
15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96 15 / 0.95
9.53 [3/8] 15.88 [5/8]
8 / 1.00
15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96 15 / 0.95
6.35 [1/4] 19.05 [3/4]**
8 / 1.00
15 / 0.99 10 / 0.99
1 / 0.99
NR
NR
7.94 [5/16] 19.05 [3/4]**
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.98
9.53 [3/8] 19.05 [3/4]**
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.99 15 / 0.98
10.6 KW
[3 Ton]
7.94 [5/16] 15.88 [5/8]
8 / 0.99
15 / 0.97 15 / 0.95 15 / 0.93 11 / 0.91
NR
9.53 [3/8] 15.88 [5/8]
8 / 0.99
15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91
NR
7.94 [5/16] 19.05 [3/4]
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.98 11 / 0.97
7 / 0.96
9.53 [3/8] 19.05 [3/4]
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96
12.7 [1/2] 19.05 [3/4]
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.97 15 / 0.96
14.1 KW
[4 Ton]
9.53 [3/8] 19.05 [3/4]
8 / 0.99
15 / 0.98 15 / 0.97 15 / 0.96 15 / 0.94 15 / 0.93
12.7 [1/2] 19.05 [3/4]
8 / 0.99
15 / 0.98 15 / 0.97 15 / 0.96 15 / 0.94 15 / 0.93
9.53 [3/8] 22.23 [7/8]
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.98 15 / 0.97
12.7 [1/2] 22.23 [7/8]
8 / 1.00
15 / 0.99 15 / 0.99 15 / 0.98 15 / 0.98 15 / 0.97
17.6 KW
[5Ton]
9.53 [3/8] 19.05 [3/4]
8 / 0.99
15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91
NR
12.7 [1/2] 19.05 [3/4]
8 / 0.99
15 / 0.97 15 / 0.95 15 / 0.93 15 / 0.91
NR
9.53 [3/8] 22.23 [7/8]
8 / 1.00
15 / 0.99 15 / 0.98 15 / 0.98 15 / 0.97 12 / 0.96
12.7 [1/2] 22.23 [7/8]
8 / 1.00
15 / 0.99 15 / 0.97 15 / 0.98 15 / 0.97 15 / 0.96
Notes:
1) Do not exceed 46 meters lineal line length.
2) *Do not exceed 15 meters vertical separation between indoor and outdoor units.
3) **19.05mm [3/4in] vapor line should only be used for 2 ton system if outdoor unit is below or at same
level as indoor unit to assure proper oil return.
4) Always use the smallest liquid line allowable to minimize refrigerant charge.
5) Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96, which are not
recommended, but are allowed.
6) Applications shared in dark gray are not recommended but to excessive, liquid or suction pressure drop.
20 SEER Variable Speed Air-Conditioners