15
4.0 INSTALLATION
4.5 Line Set Installation
Tubing
•
If tubing is to be run underground, it must be run in a
sealed watertight chase.
•
Use care in routing tubing and
DO NOT
kink or twist.
Use a good quality tubing bender on the suction line
to prevent kinking.
TEMPORARY
HANGER
PERMANENT
HANGER
•
Route the tubing using temporary hangers; then
straighten the tubing and install permanent hangers.
The tubing must be adequately supported.
•
Blow out the liquid and suction lines with dry nitro
-
gen before connecting to the outdoor unit and indoor
coil to remove debris that can plug the expansion
device.
ST-A1226-05-00
4.5.1 Important Tubing Installation Practices
Observe the following when installing correctly
sized type “L” refrigerant tubing between the outdoor unit
and indoor coil:
•
Check Table 2 for the correct suction line size and
liquid line size.
• If a portion of the liquid line passes through a
very hot area where liquid refrigerant can be
heated to form vapor, insulating the liquid line is
required.
•
Use clean, dehydrated, sealed refrigeration-grade
tubing.
•
Always keep tubing sealed until tubing is in place
and connections are to be made.
•
A high-quality biflow filter drier is included with all
R-410A heat pump units and must be installed in the
liquid line upon unit installation.
•
When replacing an R-22 system with an R-410A
system and the line set is not replaced, blow out
the lines with dry nitrogen to remove as much of
the remaining mineral oil as possible. Check for low
spots where oil may be trapped and take measures
to drain the oil from those areas.
•
If tubing has been cut, debur the ends while
holding the tubing in a position to prevent chips
from falling into tubing. Burrs such as those
caused by tubing cutters can affect performance
dramatically, particularly on small diameter liquid
lines.
•
For best operation, keep tubing run as short as
possible with a minimum number of elbows or
bends
•
Locations where the tubing will be exposed to
me
chanical damage should be avoided. If it is
necessary to use such locations, the copper tub
-
ing should be protected by a housing to prevent
damage.