9.0 DIAGNOSTICS & TROUBLESHOOTING
9.3 Status and Diagnostic Codes
Diagnostics
The error codes below will be displayed at the EcoNet™ Control Center under Service window / Current Faults
or in the Fault History and will be time and date stamped. VSODC (Variable Speed Outdoor Unit Control –
EcoNet™ control board) fault code is what will be displayed on the VSODC.
A919_O Inverter Fault -
PFC/DSP Comm Fault
•
Drive lost internal communication
between PFC and DSP
•
Check Mod Bus Cable
•
Hard Reset of Drive
•
If fault persists - replace drive
Yellow 9 Flashes
A920_O Inverter Fault -
COM/DSP Comm fault
•
Dive lost internal communication
between PFC and DSP
•
Check Mod Bus Cable
•
Hard Reset of Drive
•
If fault persists - replace drive
Yellow 8 Flashes
A921_O Inverter Fault -
PFC Temp Sensor Open
•
Sensor to PFC is either low or
open
•
Verify proper airflow over the heatsink of the
drive. Remove any obstructions.
•
Check the compressor is operating with in
specified limits.
•
3. If the problem still persists, replace the
drive.
Yellow 1 Flash
T922_O Inverter Fault -
PIM Temp Foldback
•
Drive has folded back as a result
of PFC temperature
•
Verify proper airflow over the heatsink of the
drive. Remove any obstructions.
•
Check the compressor is operating with in
specified limits.
•
3. If the problem still persists, replace the
drive.
Yellow 21 Flashes
A925_O Inverter Fault -
Compressor Model Unknow
•
Drive size and model data card
do not match
•
Incorrect Memory Card has been installed.
•
Incorrect Inverter Drive has been installed.
Yellow 22 Flases