7.9.7
Metering enable
With the metering enable function activated, the pump only runs when an external enable
contact is closed on terminal 20 and terminal 21 (see
and
Chapter 8.2.1 ‘Operating mode [Manual] (with ‘metering
). The selected operating mode does not affect the use of the
metering enable function.
Fig. 52: Configuration: Metering enable
Factory setting: Without metering enable
[Metering enable] - setting:
1.
[Main menu]
:
Chapter 7.6 ‘Main menu’ on page 66
2.
[Configuration menu]
Chapter 7.9 ‘Overview - Configuration’ on page 83
3.
Use the scrollbar to scroll to the
[Metering enable]
menu option.
4.
[Metering enable]
- select
ð
Screen switches to the
[Metering enable]
.
5.
If required, select the
‘With metering enable’
selection box.
ð
A check mark is set in the selection field.
6.
Press the button.
ð
The setting is saved, and the screen switches back to the configuration overview.
7.
Pressing the button returns to the
[Main menu]
.
8.
Pressing the button returns to the
[Operating display]
.
Control / software
93
Rev. 2-05.2018