Parameter

Description

Setting range

Default

Servo

Support for manual opening. KEY opens automatically. Adjustable in 5 steps, depen-

ding on leaf width and leaf weight. 

OFF

1…5

OFF

APuGo

Release angle Push&Go (angle push & go)

OFF,  2…10 °

OFF

ASES

1)  Blanking point Safety Element Stop (angle safety element stop). 

ASES will be set to Ao automatically if Ao is changed. 

45 °…Ao

95 °

Ao dep. (95 °)

ASER

2) Blanking area Safety Element Reversing (angle safety element reversing).

0…60 °

0 °

SeOpCo

Obstinate opening (safety element open continue). After a Safety Element Stop 

while opening, the door should continue opening (instead of closing) as soon as 

SES is inactive.  

OFF

ON

OFF

SeOpTi

Waiting time until the drive despite SeOpCo = ON 

(safety element opening time)

Closes if an obstacle blocks the door 

(only visible when SeOpCo = ON).

PERMAN

1…60 s

20 s

SESClo

Safety Element Stop while closing active/inactive 

(safety element stop closing)

ACTIVE

INACTI

INACTI

EMY-IN

Configuration of Emergency-Clamp (Opener contact) 

(emergency input)

CL - SPR  (spring)

STOP

OPEN

CL - MOT  (motor)

CL - SPR

OExStp

Step-switch function (opening element step)

OFF

OEI

OEO

KEY

RADIO

OFF

FPReset

Acknowledgement of the fire alarm via fire alarm center  

(only allowed if the door is in visual range of the fire alarm center)

OFF

ON

OFF

RC 0.1

Parameterizable relais output 1 on option print 1 (relay contact)

(only visible if relais print 0 is plugged in)

CLOSED

OPENING

OPEN

CLOSING

ERROR

PSAUTO

PSNIGHT

PSEXIT

PSOPEN

PSMANU

GONG

LOCKED

SIX30S

FP_RDY

EMY_AL

CLOSED

RC 0.2

Parameterizable relais output 2 on option print 1 (relay contact)

(only visible if relais print 0 is plugged in)

OPEN

RC 0.3

Parameterizable relais output 3 on option print 1 (relay contact)

(only visible if relais print 0 is plugged in)

ERROR

RC 0.4

Parameterizable relais output 4 on option print 1 (relay contact)

(only visible if relais print 0 is plugged in)

GONG

RC 1.1

Parameterizable relais output 1 on option print 2 (relay contact)

(only visible if relais print 1 is plugged in)

OPENING

RC 1.2

Parameterizable relais output 2 on option print 2 (relay contact)

(only visible if relais print 1 is plugged in)

CLOSING

RC 1.3

Parameterizable relais output 3 on option print 2 (relay contact)

(only visible if relais print 1 is plugged in)

PSAUTO

RC 1.4

Parameterizable relais output 4 on option print 2 (relay contact)

(only visible if relais print 1 is plugged in)

LOCKED

ETS 42

0549-990-51---60_2019.06.indd

1)

closed

open

closed

open

ASES

SER inactive

ASER

SES inac

-

tive

2)

0549-990/51

Seite 41 von 75

Montage- und Betriebsanleitung

MovCon

Dauertest Auf/Zu (moving continuous)

OFF

ON-FLT

ON-PRM

OFF

OExMAN

Annehmen von Auf-Befehlen wenn Tür manuell geöffnet wurde (nur wenn APuGo = OFF)

(opening element inside/outside manual)

OFF

ON

OFF

OEOSIR

Sicherheitselement auf Türband-Gegenseite als Öffnungselement.

Hinweis: Zum Einlernen des LZR-FLATSCAN muss dieser Paramenter auf OFF sein.

OFF

ON

OFF

PSKIZe

Nullposition der Programmstellung (Betriebsart); fixe Programmstellung, welche nur über 

Klemmen auf der Steuerung geändert werden kann (Programmwahltaster im Seitendeckel 

inaktiv).

Verwendung für externen Programmschalter (nur vier Klemmen) oder Ansteuerung der Pro-

grammstellungen über Klemmen auf der Steuerung.

(program selection klemme zero)

No Act

PSOpen

PSHand

PSAuto

PSExit

PSNigt

No Act

SCBloc

Programmwahltaster im Seitendeckel sperren (side cover block)

Toggle = Sperren/Entsperren (aktive Programmtaste während mindestens 5 Sekunden drü-

cken).

Time = Sperren (automatisch nach 5 Minuten ohne Betätigung der Programmtasten), Entsper-

ren (aktive Programmtaste während mindestens 5 Sekunden drücken).

OFF

Toggle

Time

OFF

Buzzer

Buzzer signalisiert die Türflügelbewegung (Personen mit Sehschwäche/Barrierefreiheit)

OFF

BOTH 

OPEN

CLOSE

OFF

ETS 42

0549-990-51---60_2019.06.indd

1)

closed

open

closed

open

ASES

SER inactive

ASER

SES inac

-

tive

2)

0549-990/51

Seite 41 von 75

Montage- und Betriebsanleitung

MovCon

Dauertest Auf/Zu (moving continuous)

OFF

ON-FLT

ON-PRM

OFF

OExMAN

Annehmen von Auf-Befehlen wenn Tür manuell geöffnet wurde (nur wenn APuGo = OFF)

(opening element inside/outside manual)

OFF

ON

OFF

OEOSIR

Sicherheitselement auf Türband-Gegenseite als Öffnungselement.

Hinweis: Zum Einlernen des LZR-FLATSCAN muss dieser Paramenter auf OFF sein.

OFF

ON

OFF

PSKIZe

Nullposition der Programmstellung (Betriebsart); fixe Programmstellung, welche nur über 

Klemmen auf der Steuerung geändert werden kann (Programmwahltaster im Seitendeckel 

inaktiv).

Verwendung für externen Programmschalter (nur vier Klemmen) oder Ansteuerung der Pro-

grammstellungen über Klemmen auf der Steuerung.

(program selection klemme zero)

No Act

PSOpen

PSHand

PSAuto

PSExit

PSNigt

No Act

SCBloc

Programmwahltaster im Seitendeckel sperren (side cover block)

Toggle = Sperren/Entsperren (aktive Programmtaste während mindestens 5 Sekunden drü-

cken).

Time = Sperren (automatisch nach 5 Minuten ohne Betätigung der Programmtasten), Entsper-

ren (aktive Programmtaste während mindestens 5 Sekunden drücken).

OFF

Toggle

Time

OFF

Buzzer

Buzzer signalisiert die Türflügelbewegung (Personen mit Sehschwäche/Barrierefreiheit)

OFF

BOTH 

OPEN

CLOSE

OFF

SETTINGS 

CONFIGURATION 

(CONFIG)

ECO

 ETS – Assembly Buddy

28

Содержание ETS Series

Страница 1: ...ECO ETS ASSEMBLY BUDDY AUTOMATIC SWING DOOR DRIVE SYSTEM TECHNOLOGY FOR THE DOOR...

Страница 2: ...rail pulling BS normal installation IRM Integrated smoke detector NG Version with standard arm pushing BG transom installation SRI Integrated closing sequence control 1 From 2020 2 Type of installatio...

Страница 3: ...s for fire protection doors complete sets ETS 64 R IRM SRI NG ETS 64 R IRM SRI GSD ETS 64 R IRM SRI GSZ Double leaf drives for standard and external doors ETS 42 2 ETS 73 2 Double leaf drives n for fi...

Страница 4: ...l always have him by your side the functional ECO ETS Assembly Buddy And if we were not able to answer all your questions please do not hesitate to contact us ECO ETS Assembly Buddy 49 2373 9276 899 e...

Страница 5: ......

Страница 6: ...schraube muss um 10 mm gek rzt werden wenn diese gegen den Ber hrungsschutz des Seitendeckels mit Programmwahltaster st sst Vorgehen 1 T rfl gel schliessen 2 Mittels Einstellschraube Mass X der Situat...

Страница 7: ...ANDARD pushing plug position Y INVERSE plug position X STANDARD pushing plug position Y INVERSE plug position X Lintel mounting Lintel mounting STANDARD pulling plug position X INVERSE plug position Y...

Страница 8: ...sprechend angepasst werden 5 ffnungswinkel Ao einstellen und mittels OK best tigen Achtung Schritte 4 und 5 werden durch die Montagemasse zum T r band beeinflusst 6 Falls vorhanden Low Energy Niedrige...

Страница 9: ...essage is displayed at the end of the learning trip Done x E11 14 Display should now show the following E11 shows that the set up process is not yet finished E11 15 Use the opening command to open and...

Страница 10: ...Die Kraft die erforderlich ist um eine T r manuell zu ffnen darf 150 N nicht ber schreiten Die Kraft ist als statische Kraft an der Hauptschliesskante im rechten Winkel zum T rfl gel in einer H he vo...

Страница 11: ...t verriegelt OFFEN II Der T rfl gel ffnet automatisch und bleibt in der OFFEN Position stehen _______________________________________________________________________________ F r die nachfolgenden Betr...

Страница 12: ...CABLE PLAN ECO ETS 73 MASTER ECO ETS 64 R MASTER ECO ETS Assembly Buddy 12...

Страница 13: ...CABLE PLAN ECO ETS 64 R WITH 24V 48V SIGNAL 13...

Страница 14: ...El Fb NO NC Contact load max 30V AC DC 5A Electronic lock Emergency open close stop Swing door drive ETS 42 Overview 12 Security presence stop according to ANSI acc to ANSI 156 10 without function Re...

Страница 15: ...CABLE PLAN ECO ETS 73 OPTIONAL PRINT 15...

Страница 16: ...1200mm max 3 Modules From door widths of more than 1200mm up to 1600mm max On hinge side Function stop Test output 2 Indication light green On the hinge opposite side Funktion reversing Module 3 Door...

Страница 17: ...CABLE PLAN ETS 73 n ETS 64 n ETS 42 BEA FLATSCAN LZR LASER SENSOR 17...

Страница 18: ...mB 6 D BEDIX X112 7 D BEDIX 8 24VDC X101 9 OEO 10 GND 11 24VDC 12 OEI 13 GND 14 SE 24V X105 15 SE Stop 16 SE Test 17 GND 18 SE 24V X107 19 SE Rev 20 SE Test 21 GND 22 Auto X110 23 Locked 24 Manual 25...

Страница 19: ...BEDIX X112 7 D BEDIX 8 24VDC X101 9 OEO 10 GND 11 24VDC 12 OEI 13 GND 14 SE 24V X105 15 SE Stop 16 SE Test 17 GND 18 SE 24V X107 19 SE Rev 20 SE Test 21 GND 22 Auto X110 23 Locked 24 Manual 25 One Way...

Страница 20: ...ECO ETS Assembly Buddy CABLE PLAN MOTOR LOCKS WITH DIRECT CONNECTION OF THE COIL 20...

Страница 21: ...CABLE PLAN MOTOR LOCKS WITH OWN EVALUATION CONTROL 21...

Страница 22: ...ECO ETS Assembly Buddy CABLE PLAN MOTOR LOCKS WITH SEPARATE EVALUTATION CONTROL AND POWER SUPPLY 22...

Страница 23: ...hler werden gel scht und es wird ein Einrichtvorgang Teach durchgef hrt HAND The drive and the control elements are switched off The door leaf can be opened manually The door leaf is closed from every...

Страница 24: ...k is locked ETS does not start Contactless surface button BFT Opening command inside Opening command outside ETS BFT ETS BFT 13 blue 10 blue 12 purple 9 purple 13 brown 10 brown 11 red 8 red Contactle...

Страница 25: ...selected Key switch ETS Functions Night Key Hand manual One way only OEI COM 26 26 26 NO 23 24 25 NC 22 22 22 Teach in transmitter receiver 1 Set the receiver to operating mode 3 Push programming butt...

Страница 26: ...re 0 0 0 3 5A 0 Ao Opening angle of the door angle open If the opening angle is changed in the OPEN mode the operating mode must be changed to HAND to close the door 20 190 Rod dep 95 Rod Linkage type...

Страница 27: ...t on both doors Spital Automatic sequence When an opening command is given the door that receives the the opening command is opened After this door is closed again the second door opens automatically...

Страница 28: ...n closed open ASES SER inactive A SE R SES inac tive 2 Montage und Betriebsanleitung MovCon Dauertest Auf Zu moving continuous OFF ON FLT ON PRM OFF OExMAN Annehmen von Auf Befehlen wenn T r manuell g...

Страница 29: ...pen commands when the door was opened manually only when APuGo OFF opening element inside outside manual OFF ON OFF OEOSIR Security element on hinge opposite side as opening element Note For teaching...

Страница 30: ...ses with damping If not replace hardware If yes check correct friction of the door leaf and the closing spring preload Before closing after starting up and then every 24 hours W 02 Test failed twice D...

Страница 31: ...ng cycle E14 01 Locking Electronic lock Door leaf stucks in the locking electronic lock Check function of locking electronic lock When opening from close position H 02 Inverse operation has no locking...

Страница 32: ...ription Cause Solution Testing time Reaction E30 01 30V Error 30V too low power failure Motor overload Check power supply Replace hardware Permanently A 02 30V too high 03 Error when switching on E31...

Страница 33: ...rmanetly W or F or H Options No Description Cause Solution Testing time Reaction E60 00 Relaisprint 0 Option print has been removed redirected or is defective Check if option exists Falls If defective...

Страница 34: ...ECO ETS Assembly Buddy 34...

Страница 35: ...35...