Proper operation of the water heater requires air for combustion and ventilation. Provisions
for combustion and ventilation air must comply with referenced codes and standards.
Combustion and Ventilation Air
0.29 KW of the aggregate input of all appliances within that space.
The air must be supplied through two permanent openings of equal area.
be located within 12”(30.4cm) below the ceiling.
The minimum net free area of each opening must not be less than one
square inch per 0.29 KW of the total input rating of all the appliances in
the enclosure (but not less than 100 square inches(254cm), if each opening
Buildings of unusually tight construction shall have the combustion and
ventilation air supplied from outdoors, or a freely ventilated attic or crawl
space. If air is supplied from outdoors, directly or through vertical ducts,
a minimum net free area of not less than one square inch(2.5cm) per 1.17
KW of the total input rating of all the appliances in the enclosure.
If horizontal ducts are used to communicate with the outdoors, each
opening must have a minimum net free area of not less than one square
inch(2.5cm) per 0.59 KW of the total input rating of all the appliances in the
enclosure. If ducts are used, the minimum dimensions of rectangular air
ducts shall not be less than 4”(10.1cm).
Included Parts
Verify all included parts are present (see below).
ventilation air must be made.
NOTICE: If the duct openings which supply combustion and ventilation air are to be covered with a
protective screen or grill, the net free area (openings in the material) of the covering material must be
used in determining the size of openings. Protective screening for the openings MUST NOT be smaller
than ¼”(.63cm) to prevent clogging by lint or other debris.