STEP 7: VACUUM PUMPING
Use vacuum pump
1.
Remove the valve caps on the liquid valve and gas valve and the nut of refrigerant charging vent.
2.
Connect the charging hose of piezometer to the refrigerant charging vent of gas valve and then connect
the other charging hose to the vacuum pump.
3.
Unscrew the knob Lo completely on the gauge manifold on the low pressure side.
4.
Turn on the vacuum pump to begin removing air and moisture from the system. The vacuum pump
should be equipped with a non-return valve.
5.
Open the piezometer completely and operate for 10-15min to check if the pressure of piezometer
remains in -101kPa (-76 cm Hg).
6.
Close the vacuum pump and maintain this status for 1-2min to check if the pressure of piezometer
remains in -101kPa. If the pressure decreases, there may be leakage.
7.
Remove the piezometer, open the valve core of liquid valve and gas valve completely with inner
hexagon spanner.
8.
Disconnect the kit service tubing from the unit unit service port.
9.
Tighten the screw caps of valve and refrigerant charging vent.
10. Reinstall the handle.
STEP 8: LEAKAGE DETECTION
1. With leakage detector:
Check if there is leakage with leakage detector.
2. With soap water:
If leakage detector is not available, please use soap water for leakage detection. Apply soap water at the
suspected position and keep the soap water for more than 3min. If there are air bubbles coming out of this
position, there’s a leakage.
Содержание AORI E25-09
Страница 69: ...eberg eu KARTA GWARANCYJNA URZA DZEŃ KLIMATYZACYJNYCH MARKI EBERG ...
Страница 74: ...Data przeglądu Pieczęć i podpis serwisu Uwagi adnotacje Przeglądy techniczne ...
Страница 75: ...Data naprawy Opis Pieczęć i podpis Punktu Serwisowego Naprawy ...
Страница 76: ...Climateo Sp z o o Kokotów 703 32 002 Kokotów biuro eberg eu tel 48 513 677 545 www eberg eu ...