Tighten the union nut with torque wrench by referring to the sheet below.
Hex nut diameter
Hex nut diameter Tightening torque (N.m)
Φ 6
15 ~ 20
Φ 9,52
30 ~ 40
Φ 12
45 ~ 55
Φ 16
60 ~ 65
Φ 19
70 ~ 75
STEP 5: CONNECT INDOOR AND OUTDOOR PIPE
1.
Remove the wire clip; connect the power connection wire and signal control wire (only for cooling and
heating unit) to the wiring terminal according to the color, fix them with screws.
2.
Fix the power connection wire and signal control wire with wire clip (only for cooling and heating unit).
Note:
•
After tighten the screw,pull the power cord slightly to check if it is firm.
•
Never cut the power connection wire to prolong or shorten the distance.
STEP 6: NEATEN THE PIPES
1.
The pipes should be placed along the wall, bent
reasonably and hidden possibly. Min.semidiameter of
bending the pipe is 10cm.
2.
If the outdoor unit is higher than the wall hole, you
must set a U-shaped curve in the pipe before pipe goes
into the room.