List of event codes
Information – 251
618
Warning
Battery voltage too low
Battery voltage OK
Check battery
61C
Warning
Communication with battery lost
Communication with battery
recovered
Check battery
61E
Warning
At least one breaker in battery is
open
All battery breakers are closed
Check battery
61F
Warning
Battery State Of Charge below
limit
Battery State Of Charge OK
-
620
Warning
Battery State Of Health below limit Battery State Of Health OK
Check battery
628
Warning
Battery voltage low warning
Battery voltage OK
Check battery
62A
Warning
Battery voltage high warning
Battery voltage OK
Check battery
62C
Warning
Battery charge current low
warning
Battery charge current OK
Check battery
62E
Warning
Battery charge current high
warning
Battery charge current OK
Check battery
630
Warning
Battery discharge current low
warning
Battery discharge current OK
Check battery
632
Warning
Battery discharge current high
warning
Battery discharge current OK
Check battery
634
Warning
Battery temperature low warning
Battery temperature OK
Check battery
636
Warning
Battery temperature high warning
Battery temperature OK
Check battery
638
Warning
Battery BMS failure
Battery BMS OK
Check battery
639
Warning
Battery temperature unbalanced
Battery temperature OK
Check battery
63D
Warning
Battery warning
Battery OK
Check battery
700
Warning
Inverter limitation
No current limitation
Reduce output load
701
Warning
Inverter fuse fault
Inverter fuse OK
Service required
70A
Warning
Inverter thermal overload
No power overload
Reduce output load
70C
Warning
Inverter voltage too low
Inverter voltage OK
Service required
70D
Warning
Inverter voltage too high
Inverter voltage OK
Service required
801
Warning
Load not powered
Load powered
-
803
Warning
Output breaker open
Output breaker closed
-
806
Warning
Emergency power OFF
No emergency OFF
-
808
Warning
Power overload
No power overload
Reduce output load
80D
Warning
Internal configuration failure
Internal configuration OK
Service required
80E
Warning
Overload pre-alarm
No overload pre-alarm
Reduce output load
810
Warning
Overload alarm
No overload
Reduce output load
Содержание Network-M3
Страница 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Страница 2: ......
Страница 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Страница 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Страница 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Страница 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Страница 37: ...Home Contextual help of the web interface 37 3 2 7 3 4 HE mode ESS mode 3 2 7 3 5 Maintenance bypass mode...
Страница 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Страница 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Страница 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Страница 287: ...Acronyms and abbreviations Information 287...
Страница 294: ......