List of event codes
Information – 261
7.5.4 ATS alarm log codes
7.5.4.1 Critical
Code
Severity
Active message
Non-active message
Advice
F03
Critical
Internal failure
End of internal failure
-
F08
Critical
Internal failure
End of internal failure
-
F0B
Critical
Internal failure
End of internal failure
-
F0D
Critical
In short circuit
Not in short circuit
-
F10
Critical
Load not powered
Load powered with no continuity
-
F11
Critical
Internal failure
End of internal failure
-
F13
Critical
Temperature out of range
Temperature in range
-
F1B
Critical
Off
On preferred source
-
7.5.4.2 Warning
Code
Severity
Active message
Non-active message
Advice
F00
Warning
Unsynchronized sources
Synchronized sources
-
F01
Warning
Frequency out of range
Frequency in range
-
F02
Warning
Out of range
In range
-
F04
Warning
Voltage in derated range
Voltage in normal range
-
F06
Warning
Frequency out of range
Frequency in range
-
F07
Warning
Not in range
In range
-
F09
Warning
Voltage in derated range
Voltage in normal range
-
F0C
Warning
In overload
Not in overload
-
F0F
Warning
Internal configuration failure
Internal configuration OK
-
F12
Warning
Overload Fault
No overload fault
-
F15
Warning
Input waveform is not OK
Input waveform is OK
-
To retrieve Alarm logs, navigate to
section and press the Download alarms button.
Below codes are the one to be used to add "Exceptions on events notification" on email sending configurations.
Some zeros maybe added in front of the code when displayed in emails or logs.
Содержание Network-M3
Страница 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Страница 2: ......
Страница 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Страница 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Страница 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Страница 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Страница 37: ...Home Contextual help of the web interface 37 3 2 7 3 4 HE mode ESS mode 3 2 7 3 5 Maintenance bypass mode...
Страница 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Страница 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Страница 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Страница 287: ...Acronyms and abbreviations Information 287...
Страница 294: ......