Powering down/up applications (examples)
Servicing the Network Management Module – 185
•
•
•
•
•
•
4.3.2.2 Step 1: Installation setup
4.3.2.2.1 Objective
Use load segmentation provided by the UPS to independently control the power supply of each IT equipment categories
(Applications, Database servers, Storage).
Load segmentation also allows IT equipment to restart sequentially on utility recovery (
Restart sequentially the IT equipment on
4.3.2.2.2 Resulting setup
UPS provides outlets (Group 1 and Group 2) and a primary output.
Connections can be done as described below:
Group 2: non-priority equipment
Group 1: critical equipment
Primary: critical equipment
4.3.2.3 Step 2: Agent settings
4.3.2.3.1 Objective
Ensure IT solution is shutdown gracefully.
4.3.2.3.2 Resulting setup
1. Install IPP Software on each server (Application, Database servers, Storage) and register the UPS load segment as power source:
Critical equipment: Group 1
Non-priority equipment: Group 2
Critical equipment: Entire UPS
2. Pair agent to the Network Module (
Pairing agent to the Network Module
When done, each server appears in the Agent list.
3. Navigate to
Contextual help>>>Protection>>>Agent shutdown sequencing
page
When primary shuts OFF, both group 1 and group 2 shut OFF immediately.
For examples of Agent settings, see the
Содержание Network-M3
Страница 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Страница 2: ......
Страница 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Страница 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Страница 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Страница 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Страница 37: ...Home Contextual help of the web interface 37 3 2 7 3 4 HE mode ESS mode 3 2 7 3 5 Maintenance bypass mode...
Страница 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Страница 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Страница 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Страница 287: ...Acronyms and abbreviations Information 287...
Страница 294: ......