Instruction Booklet 

IB0191004EN

Effective June 2020

EAFR-110PLV current and arc light 

sensor relay user manual 

  

EATON

 www.eaton.com

6. Connections

Figure 16. EAFR-110PLV terminals at the rear plate.

6.1 Outputs

6.1.1 Trip  relays T1  and T2

The EAFR-110PLV relay has integrated trip relays T1 and T2 for trip-

ping the circuit-breakers.  T1 and T2 relays are normally open type 

(NO).

6.1.2 Trip  relays T3  and T4

Trip relays T3 and T4 are not utilized in the EAFR-110PLV, and are 

reserved for future use.

6.1.3 High speed outputs (HSO1 and HSO2)

The EAFR-110PLV contains two high speed semiconductor outputs: 

HSO1 and HSO2.  These outputs may be utilized either for direct 

tripping of a circuit breaker or as heavy duty signaling outputs.  Due 

to the high current carrying capacity, HSO1 and HSO2 are capable of 

supplying current or light information to a maximum of 20 EAFR-100 

series units without a need for signal amplifiers.  HSO1 operation is 

dependent on the configuration select dipswitches.  For details see 

Section 3.6.

6.1.4 Binary output BO1

One binary output is available (+24 Vdc).  The binary output function 

can be configured using the dipswitches (see Section 3.5: Dipswitch 

settings).

ote: 

N

The binary output is polarity sensitive (see Section 7: Wiring diagram).

6.1.5 System failure relay SF

The system failure relay (SF) is a form C type (NO/NC) and is ener-

gized in the healthy condition.  Whenever the EAFR-110PLV detects 

a system error or disconnection of the auxiliary power supply, the 

contact changes its state.  The state of the SF relay remains the 

same until the relay returns to a healthy condition and the SF relay is 

energized again.

6.2 Inputs

6.2.1 Current measurement inputs

The EAFR-110PLV has four CT inputs for three-phase current and 

earth current measurement.  Both phase current and earth current 

inputs may be configured to 1 or 5 amps nominal current input 

using dipswitches (see Section 3.6: Dipswitch settings).  For setting 

current threshold levels refer to Section 3.5: Current threshold 

setting.  An open circuit detection feature is included, for more 

details, refer to Section 5.1: Open CT monitoring.

6.2.2 Arc sensor channels S1, S2, S3, S4, and S5

The EAFR-110PLV has four arc point sensor channels (S1, S2, S3, 

and S4).  A maximum three arc point sensors (type EAFR-01) may be 

connected to each channel.
S5 is a fiber optic I/O that is used as a fiber optic loop sensor input 

on other versions of the EAFR-110.  The EAFR-110PLV uses the TX 

output of S5 for controlling the Arc Quenching Device.  The relay 

sends a continuous light pulse to the arc quenching device for self-

supervision purposes.6.2.3 Binary Inputs (BI1 and BI2)
The EAFR-110PLV contains two binary inputs (BI1 and BI2).  The 

function of binary inputs is selected using the dipswitches accord-

ing to standard arc configurations applications (see Section 3.6).  

Typically, binary inputs are utilized for receiving the arc light informa-

tion from the EAFR-101 and EAFR-102 units, and receiving the over-

current information from the other EAFR-110PLV devices.
The inputs are activated by connecting a dc signal exceeding the 

specified nominal threshold level of the corresponding input.  The 

threshold level is 24Vdc.   The actual activation of the binary input 

occurs at 80% of the specified nominal threshold value (i.e.: 19Vdc).

6.3 Auxiliary voltage

The auxiliary power supply voltage is (110-220) Vac / (125-250) Vdc.
After powering up, the relay protection is active and operational 

within 50 ms.

Содержание EAFR-110PLV

Страница 1: ...eneral 2 3 Operation and configuration 5 4 Arc sensors 9 5 System self supervision 11 6 Connections 12 7 Wiring diagrams 13 8 Dimensions and installation 14 9 Testing 16 10 Troubleshooting guide 19 11...

Страница 2: ...uP Microprocessor 2 General The Eaton Arc Flash Relay EAFR 110PLV is a sophisticated micro processor based arc flash protection relay with combined current and arc sensing Combined current and arc se...

Страница 3: ...vice AQD for the maximum level of arc fault protection The main features of EAFR 110PLV 110 220 Vac 125 250 Vdc auxiliary power supply Three phase current inputs IL1 IL2 and IL3 1A 5A nominal One grou...

Страница 4: ...supervision Control and power supply Ig X3 12 11 10 9 8 7 6 5 4 3 2 1 1A 5A HSO1 1A 5A 1A 5A 1A 5A HSO2 T3 SW1 SW2 set x In Ig set x In Current 0 5 0 05 1 0 6 0 13 12 S1 S2 8 7 6 S3 5 4 3 S4 2 1 QD u...

Страница 5: ...ve condition If the arc sensor is activated the corresponding sensor channel LED will turn on if the activation is longer than 1 5 ms The sensor LED activation function is latched steady light To clea...

Страница 6: ...formed Also activated by pressure information Check why the sensor activated check the sensor continuity or perform system setup see Section 3 3 1 Auto configuration System setup S4 Amber Normal statu...

Страница 7: ...n previous memorized set up a dip switch anyone must be moved back and forth prior to performing auto configuration Timeout allowing new configuration is one minute Reconfiguration with more connectio...

Страница 8: ...trip criteria channel 3 in EAFR 110F Trip on light only Trip on light and over current Both signals are required simultaneously to trip 5 a b Selection of standard arc configuration type Standard arc...

Страница 9: ...as completely as possible One sensor per closed metal clad compartment should be utilized In open spaces such as the bus bar section arc sensors should be mounted maximum 2 m 6 5 ft apart The factory...

Страница 10: ...see Figure 8 Figure 8 EAFR 01 sensor connection step 2 3 Connect the other end of the cable to a sensor channel on the EAFR 101 or EAFR 110PLV relay see Figure 9 Figure 9 EAFR 01 sensor connection ste...

Страница 11: ...the ERROR LED is illuminated If a fiber sensor failure occurs the unit will go into Error mode The ERROR LED will turn on the SF relay will release and the corresponding faulty fiber sensor channel L...

Страница 12: ...gized again 6 2 Inputs 6 2 1 Current measurement inputs The EAFR 110PLV has four CT inputs for three phase current and earth current measurement Both phase current and earth current inputs may be conf...

Страница 13: ...iring diagrams Figure 17 EAFR 110PLV wiring diagram A A T2 CBFP T3 SF T1 T4 X2 1 2 13 12 11 10 9 8 7 6 X1 11 10 9 8 7 6 5 4 3 2 1 UAUX S1 S2 S3 S4 S5 Station battery _ EAFR 110PLV _ _ _ IL1 IL2 IL3 Ig...

Страница 14: ...t sensor relay user manual EATON www eaton com 8 Dimensions and installation The EAFR 110PLV is door mounted in standard 19 in 482 6 mm rack height of 4U and 1 4 of a relay wide Figure 18 EAFR 102 dim...

Страница 15: ...Figure 19 EAFR 110PLV dimensions in millimeters inches 3 D view POWER ERROR TRIP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 2...

Страница 16: ...corresponding sensor channel indication LED status is changed to ON 4 Verify the relay output s activation s by checking the circuit breaker status or by monitoring the trip contact status The circuit...

Страница 17: ...d configured to send light information 13 Press the SET push button to reset all indications and latches 14 If the binary input BI2 is utilized for master trip to activate the BI2 verify that a trip h...

Страница 18: ...s Sensor channel 1 setting Sensor channel 2 3 4 setting Circuit breaker failure protection CBFP in use yes no Object activated LED indication T1 and T2 active BO1 active Sensor channel 1 Sensor 1 Sens...

Страница 19: ...stance 10 m Power consumption of current inputs circuit 10 m 11 4 Trip relays T1 and T2 Number 3 NO 1 NC or 4 NO Rated voltage 250 Vac dc Continuous carry 5 A Make and carry for 0 5 s 30 A Make and ca...

Страница 20: ...degree back IP 20 Dimensions W x H x D mm W x H x D in 102 x 157 x 164 mm 4 02 x 6 18 x 6 46 in Package dimensions W x H x D mm in 230 x 120 x 210 mm 9 06 x 6 18 x 6 46 in Weight 0 7 kg 24 69 oz 1 0...

Страница 21: ...or 20 m 65 62 ft EAFR 06 25 65C2013G04 Arc light plastic fiber sensor 25 m 82 02 ft EAFR 06 30 65C2013G05 Arc light plastic fiber sensor 30 m 93 43ft EAFR 06 35 65C2013G06 Arc light plastic fiber sens...

Страница 22: ...ement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOS...

Отзывы: