Instruction Booklet 

IB0191004EN

Effective June 2020

EAFR-110PLV current and arc light 

sensor relay user manual 

  

EATON

 www.eaton.com

Figure 13. EAFR-01 sensor connection step 7.

8.  After completing the system auto-configuration setting, close 

both end side covers back (see  Figure 14).

Figure 14. EAFR-01 sensor connection step 8.

9.  A maximum amount of three arc sensors can be daisy-chained 

to the same sensor input on the EAFR-101 relay (see Figure 15).

Figure 15. EAFR-01 sensor connection step 9.

Auto-configuration is a part of the self-supervision function which 

ensures that all connections and sensors are fully functional and 

ready to operate at all times.

5. System self-supervision

The EAFR-110PLV includes an extensive self-supervision feature.  

Self-supervision includes both internal functions and external 

connections.  The self-supervision module monitors the power 

supply, HW malfunctions, SW malfunctions, the binary input connec-

tions, and sensor problems.  Dipswitch settings are also supervised 

by comparing the actual values with stored non-volatile memory data 

(see Section 3.3.1: Auto configuration [System setup]).
In a healthy condition, the POWER LED is on and the system failure 

(SF) relay is energized.  If the self-supervision function detects a 

faulty condition or the power supply fails, the self-supervision relay 

is released and the ERROR LED is illuminated.
If a fiber sensor failure occurs, the unit will go into Error mode.  

The ERROR LED will turn on, the SF relay will release, and the 

corresponding faulty fiber sensor channel LED will start blinking.  In 

this situation, the unit is still in protection mode, but with the faulty 

fiber sensor channel blocked.  If the error is resolved, the unit will 

automatically clear the SF-status.  This means that the SF relay will 

energize and the ERROR LED will turn off.  If one or more of the 

sensors are disconnected, the healthy sensors remain in use and 

unit remains operational accordingly.  The EAFR-110PLV will remain 

in the Error mode until the disconnected sensors are repaired.
If a dipswitch setting is changed after the auto-configuration func-

tion (see Section 3.3.1: Auto configuration [System setup]) has 

been executed, the unit will go into SF-alarm mode.  The configured 

(stored) setting is however still valid and the unit is still operational.  

The SF relay can be reset by pressing and holding the “SET” button 

for two seconds.

5.1 Open CT monitoring

If there is a current flow of more than 0.2 x In, the relay assumes 

that the switchgear is energized.  In this case, phases IL1, IL2, and 

IL3 are monitored and supervised for open connection (no current 

flow).
If one or two of the three phases is 0 while the other(s) remain 

above 0.2 x In, the relay will issue an open CT alarm.
When an open CT alarm is issued, the SF-relay is released, the 

ERROR LED turned on, and corresponding IL1, IL2, and IL3 LEDs 

starts blinking.

SET push button

Содержание EAFR-110PLV

Страница 1: ...eneral 2 3 Operation and configuration 5 4 Arc sensors 9 5 System self supervision 11 6 Connections 12 7 Wiring diagrams 13 8 Dimensions and installation 14 9 Testing 16 10 Troubleshooting guide 19 11...

Страница 2: ...uP Microprocessor 2 General The Eaton Arc Flash Relay EAFR 110PLV is a sophisticated micro processor based arc flash protection relay with combined current and arc sensing Combined current and arc se...

Страница 3: ...vice AQD for the maximum level of arc fault protection The main features of EAFR 110PLV 110 220 Vac 125 250 Vdc auxiliary power supply Three phase current inputs IL1 IL2 and IL3 1A 5A nominal One grou...

Страница 4: ...supervision Control and power supply Ig X3 12 11 10 9 8 7 6 5 4 3 2 1 1A 5A HSO1 1A 5A 1A 5A 1A 5A HSO2 T3 SW1 SW2 set x In Ig set x In Current 0 5 0 05 1 0 6 0 13 12 S1 S2 8 7 6 S3 5 4 3 S4 2 1 QD u...

Страница 5: ...ve condition If the arc sensor is activated the corresponding sensor channel LED will turn on if the activation is longer than 1 5 ms The sensor LED activation function is latched steady light To clea...

Страница 6: ...formed Also activated by pressure information Check why the sensor activated check the sensor continuity or perform system setup see Section 3 3 1 Auto configuration System setup S4 Amber Normal statu...

Страница 7: ...n previous memorized set up a dip switch anyone must be moved back and forth prior to performing auto configuration Timeout allowing new configuration is one minute Reconfiguration with more connectio...

Страница 8: ...trip criteria channel 3 in EAFR 110F Trip on light only Trip on light and over current Both signals are required simultaneously to trip 5 a b Selection of standard arc configuration type Standard arc...

Страница 9: ...as completely as possible One sensor per closed metal clad compartment should be utilized In open spaces such as the bus bar section arc sensors should be mounted maximum 2 m 6 5 ft apart The factory...

Страница 10: ...see Figure 8 Figure 8 EAFR 01 sensor connection step 2 3 Connect the other end of the cable to a sensor channel on the EAFR 101 or EAFR 110PLV relay see Figure 9 Figure 9 EAFR 01 sensor connection ste...

Страница 11: ...the ERROR LED is illuminated If a fiber sensor failure occurs the unit will go into Error mode The ERROR LED will turn on the SF relay will release and the corresponding faulty fiber sensor channel L...

Страница 12: ...gized again 6 2 Inputs 6 2 1 Current measurement inputs The EAFR 110PLV has four CT inputs for three phase current and earth current measurement Both phase current and earth current inputs may be conf...

Страница 13: ...iring diagrams Figure 17 EAFR 110PLV wiring diagram A A T2 CBFP T3 SF T1 T4 X2 1 2 13 12 11 10 9 8 7 6 X1 11 10 9 8 7 6 5 4 3 2 1 UAUX S1 S2 S3 S4 S5 Station battery _ EAFR 110PLV _ _ _ IL1 IL2 IL3 Ig...

Страница 14: ...t sensor relay user manual EATON www eaton com 8 Dimensions and installation The EAFR 110PLV is door mounted in standard 19 in 482 6 mm rack height of 4U and 1 4 of a relay wide Figure 18 EAFR 102 dim...

Страница 15: ...Figure 19 EAFR 110PLV dimensions in millimeters inches 3 D view POWER ERROR TRIP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 2...

Страница 16: ...corresponding sensor channel indication LED status is changed to ON 4 Verify the relay output s activation s by checking the circuit breaker status or by monitoring the trip contact status The circuit...

Страница 17: ...d configured to send light information 13 Press the SET push button to reset all indications and latches 14 If the binary input BI2 is utilized for master trip to activate the BI2 verify that a trip h...

Страница 18: ...s Sensor channel 1 setting Sensor channel 2 3 4 setting Circuit breaker failure protection CBFP in use yes no Object activated LED indication T1 and T2 active BO1 active Sensor channel 1 Sensor 1 Sens...

Страница 19: ...stance 10 m Power consumption of current inputs circuit 10 m 11 4 Trip relays T1 and T2 Number 3 NO 1 NC or 4 NO Rated voltage 250 Vac dc Continuous carry 5 A Make and carry for 0 5 s 30 A Make and ca...

Страница 20: ...degree back IP 20 Dimensions W x H x D mm W x H x D in 102 x 157 x 164 mm 4 02 x 6 18 x 6 46 in Package dimensions W x H x D mm in 230 x 120 x 210 mm 9 06 x 6 18 x 6 46 in Weight 0 7 kg 24 69 oz 1 0...

Страница 21: ...or 20 m 65 62 ft EAFR 06 25 65C2013G04 Arc light plastic fiber sensor 25 m 82 02 ft EAFR 06 30 65C2013G05 Arc light plastic fiber sensor 30 m 93 43ft EAFR 06 35 65C2013G06 Arc light plastic fiber sens...

Страница 22: ...ement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOS...

Отзывы: