Instruction Booklet 

IB0191004EN

Effective June 2020

EAFR-110PLV current and arc light 

sensor relay user manual 

  

EATON

 www.eaton.com

10. Troubleshooting  guide

Table 5.  Troubleshooting guide.

Problem

Check

Cross reference

Sensor does not activate 

when testing.

Sensor cable wiring.

Section 4.6 of this 

manual

Camera (or other 

test equipment) flash 

intensity.

Section 9 of this 

manual

Trip relay(s) does not 

operate even if sensor is 

activated.

Dipswitch settings and 

current threshold set-

points.

Section 3.6 and 6 of 

this manual.

Current measurement 

indicator LED is 

continuously on.

Current threshold set-

points.

Section 3.5 of this 

manual.

Current measurement 

indicator LED is blinking.

Proper connection of 

three phase currents.

Section 5.1 of this 

manual.

11. Technical  data

11.1 Protection stages

Trip time using HSO

2 ms*

Trip time using mechanical trip relays

7 ms*

Reset time (light stage)

1 ms 

Reset time (over-current stages)

50 ms

Protection operational after power up

50 ms

* = Total trip time using arc light or phase/earth over-current from 

EAFR-110PLV and arc light.

11.2 Auxiliary voltage

Vaux

(110-220) Vac / (125-250) Vdc ± 20%

Maximum interruption 

100 ms

Maximum power consumption

5 W, <10 mΩ

Standby Ccurrent

90 mA

11.3 Current measuring circuits

Nominal current

1 or 5 A

Rated frequency

2 to 1,000 Hz

Number of inputs

3 (phase) + 1 (earth)

Thermal withstand continuous

30 A

Thermal withstand 1 s

500 A

Thermal withstand 10 s

100 A

Phase over-current setting range

0.5 to 6* In

Earth over-current setting range

0.05 to 2 *In

Measurement accuracy

10%

Rated AC burden (VA)

Input resistance 10 mΩ

Power consumption of current inputs circuit

<10 mΩ

11.4 Trip  relays T1  and T2

Number

3 NO + 1 NC or 4 NO

Rated voltage

250 Vac/dc

Continuous carry

5 A

Make and carry for 0.5 s

30 A

Make and carry for 3 s

16 A

Breaking capacity DC, when time constant 

L/R = 40 ms

40 W; 0.36 A at 110 Vdc

Contact material

AgNi 90/10

11.5 High speed outputs HSO1 and HSO2

Number

2

Rated voltage

250 Vdc

Continuous carry

2 A

Make and carry for 0.5 s

15 A

Make and carry for 3s

6 A

Breaking capacity DC, when time constant 

L/R = 40 ms

1 A / 110 W

Contact material

Semiconductor

11.6 Binary output BO1

Rated voltage

+24 Vdc

Rated current 

20 mA (max)

Number of outputs

1

11.7 Binary inputs BI1 and BI2

Rated voltage

24 

Rated current 

3 mA

Number of inputs

2

11.8 Disturbance tests

EMC test

CE approved and tested according to 

EN 50081-2, EN 50082-2.

Emission
- Conducted (EN 55011 class A)

0.15 - 30 MHz

- Emitted (EN 55011 class A)

30 - 1 000 MHz

Immunity 
- Static discharge (ESD) (according 

to IEC244-22-2 and EN61000-4-2, 

class III)

Air discharge 15 kV.

Contact discharge 8 kV.

- Fast transients (EFT) (according to 

EN61000-4-4, class III and IEC801-4, 

level 4)

Power supply input 4 kV, 5/50 ns

Other inputs and outputs 4 kV,  5/50 

ns

- Surge (according to EN61000-4-5 

[09/96], level 4)

Between wires 2 kV / 1.2/50 µs.

Between wire and earth 4 kV / 1.2/50 

µs.

- RF electromagnetic field test  

(according. to EN 61000-4-3, class III)

f = 80 to 1,000 MHz 10 V /m

- Conducted RF field (according. to EN 

61000-4-6, class III)

f = 150 kHz to 80 MHz 10 V

11.9 Voltage  tests

Insulation test voltage Acc - to IEC 60255-5

2 kV, 50 Hz, 1 min

Impulse test voltage Acc - to IEC 60255-5

5 kV, 1.2/50 us, 0.5 J

11.10 Mechanical tests

Vibration test

2 to 13.2 Hz ± 3.5 mm (0.14 in.)

13.2 to 100 Hz, ± 1.0 g (0.04 oz)

Shock/bump test acc. to IEC 60255-21-2

20 g, 1,000 bumps/dir.

Содержание EAFR-110PLV

Страница 1: ...eneral 2 3 Operation and configuration 5 4 Arc sensors 9 5 System self supervision 11 6 Connections 12 7 Wiring diagrams 13 8 Dimensions and installation 14 9 Testing 16 10 Troubleshooting guide 19 11...

Страница 2: ...uP Microprocessor 2 General The Eaton Arc Flash Relay EAFR 110PLV is a sophisticated micro processor based arc flash protection relay with combined current and arc sensing Combined current and arc se...

Страница 3: ...vice AQD for the maximum level of arc fault protection The main features of EAFR 110PLV 110 220 Vac 125 250 Vdc auxiliary power supply Three phase current inputs IL1 IL2 and IL3 1A 5A nominal One grou...

Страница 4: ...supervision Control and power supply Ig X3 12 11 10 9 8 7 6 5 4 3 2 1 1A 5A HSO1 1A 5A 1A 5A 1A 5A HSO2 T3 SW1 SW2 set x In Ig set x In Current 0 5 0 05 1 0 6 0 13 12 S1 S2 8 7 6 S3 5 4 3 S4 2 1 QD u...

Страница 5: ...ve condition If the arc sensor is activated the corresponding sensor channel LED will turn on if the activation is longer than 1 5 ms The sensor LED activation function is latched steady light To clea...

Страница 6: ...formed Also activated by pressure information Check why the sensor activated check the sensor continuity or perform system setup see Section 3 3 1 Auto configuration System setup S4 Amber Normal statu...

Страница 7: ...n previous memorized set up a dip switch anyone must be moved back and forth prior to performing auto configuration Timeout allowing new configuration is one minute Reconfiguration with more connectio...

Страница 8: ...trip criteria channel 3 in EAFR 110F Trip on light only Trip on light and over current Both signals are required simultaneously to trip 5 a b Selection of standard arc configuration type Standard arc...

Страница 9: ...as completely as possible One sensor per closed metal clad compartment should be utilized In open spaces such as the bus bar section arc sensors should be mounted maximum 2 m 6 5 ft apart The factory...

Страница 10: ...see Figure 8 Figure 8 EAFR 01 sensor connection step 2 3 Connect the other end of the cable to a sensor channel on the EAFR 101 or EAFR 110PLV relay see Figure 9 Figure 9 EAFR 01 sensor connection ste...

Страница 11: ...the ERROR LED is illuminated If a fiber sensor failure occurs the unit will go into Error mode The ERROR LED will turn on the SF relay will release and the corresponding faulty fiber sensor channel L...

Страница 12: ...gized again 6 2 Inputs 6 2 1 Current measurement inputs The EAFR 110PLV has four CT inputs for three phase current and earth current measurement Both phase current and earth current inputs may be conf...

Страница 13: ...iring diagrams Figure 17 EAFR 110PLV wiring diagram A A T2 CBFP T3 SF T1 T4 X2 1 2 13 12 11 10 9 8 7 6 X1 11 10 9 8 7 6 5 4 3 2 1 UAUX S1 S2 S3 S4 S5 Station battery _ EAFR 110PLV _ _ _ IL1 IL2 IL3 Ig...

Страница 14: ...t sensor relay user manual EATON www eaton com 8 Dimensions and installation The EAFR 110PLV is door mounted in standard 19 in 482 6 mm rack height of 4U and 1 4 of a relay wide Figure 18 EAFR 102 dim...

Страница 15: ...Figure 19 EAFR 110PLV dimensions in millimeters inches 3 D view POWER ERROR TRIP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 2...

Страница 16: ...corresponding sensor channel indication LED status is changed to ON 4 Verify the relay output s activation s by checking the circuit breaker status or by monitoring the trip contact status The circuit...

Страница 17: ...d configured to send light information 13 Press the SET push button to reset all indications and latches 14 If the binary input BI2 is utilized for master trip to activate the BI2 verify that a trip h...

Страница 18: ...s Sensor channel 1 setting Sensor channel 2 3 4 setting Circuit breaker failure protection CBFP in use yes no Object activated LED indication T1 and T2 active BO1 active Sensor channel 1 Sensor 1 Sens...

Страница 19: ...stance 10 m Power consumption of current inputs circuit 10 m 11 4 Trip relays T1 and T2 Number 3 NO 1 NC or 4 NO Rated voltage 250 Vac dc Continuous carry 5 A Make and carry for 0 5 s 30 A Make and ca...

Страница 20: ...degree back IP 20 Dimensions W x H x D mm W x H x D in 102 x 157 x 164 mm 4 02 x 6 18 x 6 46 in Package dimensions W x H x D mm in 230 x 120 x 210 mm 9 06 x 6 18 x 6 46 in Weight 0 7 kg 24 69 oz 1 0...

Страница 21: ...or 20 m 65 62 ft EAFR 06 25 65C2013G04 Arc light plastic fiber sensor 25 m 82 02 ft EAFR 06 30 65C2013G05 Arc light plastic fiber sensor 30 m 93 43ft EAFR 06 35 65C2013G06 Arc light plastic fiber sens...

Страница 22: ...ement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOS...

Отзывы: