3.3 Push-button description

The EAFR-110PLV contains one single push-button (SET) that can be 

used for all operational functions of the relay.  The SET push-button 

is used to initialize the auto-configuration of the system (see Section 

3.3.1) and for resetting the indicators and latched output relays.

3.3.1 Auto configuration (system setup)

When all current circuits, sensors, and binary lines have been 

connected, an auto-configuration procedure must be executed.  The 

initialization sequence is performed by pressing the SET button 

for two seconds, and the EAFR-110PLV sensor LEDs and BI1/BI2 

LEDs start blinking.  The relay scans these inputs to see if they are 

connected and, when an input is detected, the corresponding LEDs 

are illuminated to mark that a connection was found.  The inputs 

without a connection continue blinking during the remaining three 

seconds.  After five seconds, all LEDs are turned off.  During this 

system setup, the dipswitch settings are also stored in non-volatile 

memory.
All sensor inputs will remain operational even when not auto 

configured.  The auto configuration is only used for self-supervision 

purposes.

ote: 

N

To redo auto configuration for a relay containing less connections 

(binary inputs/outputs or sensors) than in previous memorized set-up, a 

dip-switch (anyone) must be moved back and forth prior to performing 

auto-configuration.  Timeout allowing new configuration is one minute.  

Reconfiguration with more connections is allowed without moving a 

dip-switch.

3.4 Reset

All LED indications and latched trip relays are reset by pressing the 

SET button for one second.  Otherwise, the latched trip relays will 

remain activated until auxiliary power is disconnected.  All LED indi-

cations will remain active until a reset is performed by the operator, 

even in the case of disconnecting the auxiliary power supply (see 

Section 3.7: Non-volatile memory).

3.5 Current threshold setting

The EAFR-110PLV relay has four current measurement inputs utilized 

for three-phase and earth current measurement.  Both phase current 

and earth current measurements are utilized as the second trip 

criteria in an arc protection system in order to avoid a trip caused by 

natural light sources.  Phase over-current threshold is typically set 50 

% above the highest load current (In).  Earth fault over-current is very 

sensitive.  Set points are set using potentiometers (see  

Figure 3).  An accurate setting is obtained by injecting the desired 

set value using a relay test set to phase and earth current inputs of 

the EAFR-110PLV, simultaneously adjusting the potentiometers until 

phase and earth current indication LEDs are illuminated.
The setting range for the phase over-current stage is 0.5 to 6 xIn.  

The setting range for earth fault over-current stage is 0.05 to 2 xIn.

Figure 3. EAFR-110PLV over-current setting potentiometers.

Содержание EAFR-110PLV

Страница 1: ...eneral 2 3 Operation and configuration 5 4 Arc sensors 9 5 System self supervision 11 6 Connections 12 7 Wiring diagrams 13 8 Dimensions and installation 14 9 Testing 16 10 Troubleshooting guide 19 11...

Страница 2: ...uP Microprocessor 2 General The Eaton Arc Flash Relay EAFR 110PLV is a sophisticated micro processor based arc flash protection relay with combined current and arc sensing Combined current and arc se...

Страница 3: ...vice AQD for the maximum level of arc fault protection The main features of EAFR 110PLV 110 220 Vac 125 250 Vdc auxiliary power supply Three phase current inputs IL1 IL2 and IL3 1A 5A nominal One grou...

Страница 4: ...supervision Control and power supply Ig X3 12 11 10 9 8 7 6 5 4 3 2 1 1A 5A HSO1 1A 5A 1A 5A 1A 5A HSO2 T3 SW1 SW2 set x In Ig set x In Current 0 5 0 05 1 0 6 0 13 12 S1 S2 8 7 6 S3 5 4 3 S4 2 1 QD u...

Страница 5: ...ve condition If the arc sensor is activated the corresponding sensor channel LED will turn on if the activation is longer than 1 5 ms The sensor LED activation function is latched steady light To clea...

Страница 6: ...formed Also activated by pressure information Check why the sensor activated check the sensor continuity or perform system setup see Section 3 3 1 Auto configuration System setup S4 Amber Normal statu...

Страница 7: ...n previous memorized set up a dip switch anyone must be moved back and forth prior to performing auto configuration Timeout allowing new configuration is one minute Reconfiguration with more connectio...

Страница 8: ...trip criteria channel 3 in EAFR 110F Trip on light only Trip on light and over current Both signals are required simultaneously to trip 5 a b Selection of standard arc configuration type Standard arc...

Страница 9: ...as completely as possible One sensor per closed metal clad compartment should be utilized In open spaces such as the bus bar section arc sensors should be mounted maximum 2 m 6 5 ft apart The factory...

Страница 10: ...see Figure 8 Figure 8 EAFR 01 sensor connection step 2 3 Connect the other end of the cable to a sensor channel on the EAFR 101 or EAFR 110PLV relay see Figure 9 Figure 9 EAFR 01 sensor connection ste...

Страница 11: ...the ERROR LED is illuminated If a fiber sensor failure occurs the unit will go into Error mode The ERROR LED will turn on the SF relay will release and the corresponding faulty fiber sensor channel L...

Страница 12: ...gized again 6 2 Inputs 6 2 1 Current measurement inputs The EAFR 110PLV has four CT inputs for three phase current and earth current measurement Both phase current and earth current inputs may be conf...

Страница 13: ...iring diagrams Figure 17 EAFR 110PLV wiring diagram A A T2 CBFP T3 SF T1 T4 X2 1 2 13 12 11 10 9 8 7 6 X1 11 10 9 8 7 6 5 4 3 2 1 UAUX S1 S2 S3 S4 S5 Station battery _ EAFR 110PLV _ _ _ IL1 IL2 IL3 Ig...

Страница 14: ...t sensor relay user manual EATON www eaton com 8 Dimensions and installation The EAFR 110PLV is door mounted in standard 19 in 482 6 mm rack height of 4U and 1 4 of a relay wide Figure 18 EAFR 102 dim...

Страница 15: ...Figure 19 EAFR 110PLV dimensions in millimeters inches 3 D view POWER ERROR TRIP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 2...

Страница 16: ...corresponding sensor channel indication LED status is changed to ON 4 Verify the relay output s activation s by checking the circuit breaker status or by monitoring the trip contact status The circuit...

Страница 17: ...d configured to send light information 13 Press the SET push button to reset all indications and latches 14 If the binary input BI2 is utilized for master trip to activate the BI2 verify that a trip h...

Страница 18: ...s Sensor channel 1 setting Sensor channel 2 3 4 setting Circuit breaker failure protection CBFP in use yes no Object activated LED indication T1 and T2 active BO1 active Sensor channel 1 Sensor 1 Sens...

Страница 19: ...stance 10 m Power consumption of current inputs circuit 10 m 11 4 Trip relays T1 and T2 Number 3 NO 1 NC or 4 NO Rated voltage 250 Vac dc Continuous carry 5 A Make and carry for 0 5 s 30 A Make and ca...

Страница 20: ...degree back IP 20 Dimensions W x H x D mm W x H x D in 102 x 157 x 164 mm 4 02 x 6 18 x 6 46 in Package dimensions W x H x D mm in 230 x 120 x 210 mm 9 06 x 6 18 x 6 46 in Weight 0 7 kg 24 69 oz 1 0...

Страница 21: ...or 20 m 65 62 ft EAFR 06 25 65C2013G04 Arc light plastic fiber sensor 25 m 82 02 ft EAFR 06 30 65C2013G05 Arc light plastic fiber sensor 30 m 93 43ft EAFR 06 35 65C2013G06 Arc light plastic fiber sens...

Страница 22: ...ement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOS...

Отзывы: